Network

Management Card

User Manual

5 Configuring a set of cards with Mupgrade

This feature is particularly useful to configure large UPSs / STSs installed base.

The Remote configuration features of Mupgrade allows you to import, modify and export configuration files from and to Network Management Cards.

Configure all your Network Management Cards in four step :

1.Configure a Network Management Card located on the network through the html interface to create a master configuration..

2.Import this configuration from the master card in Mupgrade.

3.Edit and change some parameters , select the fields which must be overwritten in the destination cards and save the new configuration in a file.

4.Export the new configuration to other cards which have same firmware release as the master card Read the relevant documentation available for download on the www.apc.com web site.

6 Configuration in local mode and via Telnet or SSH

6.1Configuration in local mode

Use the cable supplied with the card.

Connect the card to a computer equipped with a hyper-terminal type emulator. The serial link should be set at 9600 bauds, 8 bits, no parity, 1 stop bit and no flow control.

Check that UPS power is on.

A few seconds after terminal opening, press the "Enter” button. The menu asks you to enter your password (MGEUPS by default), and then press Enter”.

The card will disconnect itself after 3 minutes of inactivity.

The menu is in English only.

+===========================================================================

+

[ MGE UPS SYSTEMS SNMP/Web agent Configuration menu ] +===========================================================================

+

Enter Password: ******

+===========================================================================

+

[ MGE UPS SYSTEMS SNMP/Web agent Configuration menu ] +===========================================================================

+

1.Agent Configuration

2.UPS/STS Parameters

3.Access Control Table

Network Management Card – User Manual

34003676EN/HA

Page 65/81

Page 65
Image 65
Schneider Electric 66074, 66846 user manual Configuring a set of cards with Mupgrade, Configuration in local mode