State Industries SUF-100-250, SUF-60-120 instruction manual Sidewall Termination Installation

Models: SUF-60-120 SUF-100-250

1 80
Download 80 pages 61 Kb
Page 29
Image 29
Sidewall Termination Installation

Sidewall Termination Installation

1. Determine the location for the termination(s).

Note: The standard vent and intake air terminations are of

different design, see Figure 22 on page 27.

2. If installing only vent (exhaust) piping in a Power Vent

configuration through a sidewall; ensure that all exterior

sidewall clearance requirements for the termination, shown

in Figure 48 on page 36, are being maintained. These

clearances and those cited by local and national codes must

be maintained.

3. If installing both intake air and vent piping in a Direct Vent

configuration through a sidewall; ensure that all exterior

sidewall clearance requirements for the terminations, shown

in Figure 49 on page 37, for the vent and intake air termination

are being maintained. These clearances and those cited by

local and national codes must be maintained.

4. If installing both an intake air and vent termination in a

Direct Vent configuration through a sidewall there must

be a minimum of 24 inches (61 cm) separation, measured

on vertical center line, between the intake air and vent

terminations, see Figure 26.

Note: In colder climates this separation should be increased

to at least 48 inches (122 cm) between the intake air and

vent termination or any other appliance vent that discharges

moisture-laden air such as clothes dryers. This will reduce

possibility of frost over from side winds blowing exhaust

vapors to the intake air termination and is recommended for

Canadian installations.

5. If installing both intake air and vent terminations in a Direct

7.Cut a 4 inch (10 cm) diameter hole for 3 inch pipe or 5 inch (13 cm) diameter hole for 4 inch pipe where the pipe(s) will pass through the wall.

Note: Beware of concealed wiring and piping when cutting through the wall.

8.Cut a length(s) of pipe being installed 3.5 inches (8.9 cm) to 9.5 inches (24.1 cm) longer than the wall thickness at the opening. See Figure 27.

Note: Vent Termination – exhaust gases of this water heater are less than 140°F. In cold climates water vapor in the exhaust gases will condense into a cloud of vapor where the vent exits the building. This vapor can gradually discolor exterior building surfaces. The vent termination should be located where this vapor cloud and potential discoloration are not a concern. Extending the exposed vent piping up to a maximum of 6 inches (15.2 cm) from the wall helps vapor from being trapped along a building’s face. To avoid this problem, the vent can also be terminated vertically through the roof, see Vertical Termination Installation on page 27.

9.Cement the intake air and/or vent termination to the section(s) of pipe cut to length in the above Step.

10.Slide the included metal wall plate(s) over the pipe(s) to stop against the intake air and/or vent termination. Place some silicone caulking (field supplied) on the back of the wall plate(s) to secure it to the wall.

11.Working from outside, slide the pipe and termination(s) assembled in the above steps through the wall. Ensure the termination(s) is pointed down towards the ground. See Figure 27.

Vent configuration through a sidewall the intake air and

vent terminations must be installed at the same elevation

measured on horizontal center line - see Figure 26.

VENT (EXHAUST)

INTAKE AIR

TERMINATION

TERMINATION

 

ELEVATION

 

INSTALL ON

 

CENTERLINE

METAL PLATES INSTALL INSIDE AND/OR OUTSIDE

FROM

WATER

HEATER

COUPLING SIDEWALL TERMINATION INSTALLATION

INTERIOR WALL Manual background

INCREASE EXPOSED VENT PIPING UP TO A MAXIMUM OF 6 INCHES (15.2 cm) FROM WALL TO HELP PREVENT VAPOR FROM DISCOLORING THE WALL SURFACE IN COLDER CLIMATES

FACTORY SUPPLIED STANDARD TERMINATION POINTED DOWN TOWARDS THE GROUND

Manual background EXTERIOR WALL

KEEP INTAKE AND VENT

TERMINATION SCREENS

CLEAR OF DEBRIS

24 INCHES (61 cm) MINIMUM

48 INCHES (122 cm) IN COLDER CLIMATES

SIDEWALL TERMINATION - DIRECT VENT

STANDARD TERMINATIONS

Figure 26

6.When the intake air and/or vent piping from multiple water heaters will terminate at the same location through a sidewall, the vent terminations can be grouped together in close proximity - 0 inches/touching. The intake air terminations can also be grouped together in close proximity - 0 inches/ touching.

However, the distance between the closest vent and intake air terminations must be a minimum of 24 inches (61 cm). In colder climates this separation should be increased to at least 48 inches (122 cm). See Figure 26.

SIDEWALL TERMINATION INSTALLATION

INTAKE AIR AND/OR VENT (EXHAUST)

Figure 27

12.Place a bead of silicone caulking (field supplied) around the gap between the installed pipe(s) and the wall. Apply enough to fill the gap between the pipe(s) and wall.

13.Press the wall plate flush against the outside wall.

14.Working from the inside apply enough silicone caulking on the back of the interior wall plate(s) to hold it in place and slide the wall plate over the installed pipe(s).

15.Install a coupling to the end of the pipe(s) inside the building. Before the silicone caulking has time to completely set go outside the building and ensure the termination(s) is still pointing down towards the ground. See Figure 27.

16.Return to Power Vent Installation on page 25 or Direct Vent Installation on page 25 to complete the installation of the intake air and/or vent piping between the termination(s) and the water heater.

29

Page 29
Image 29
State Industries SUF-100-250, SUF-60-120 instruction manual Sidewall Termination Installation