State Industries SUF-60-120, SUF-100-250 Btu/hr MODELS, Front, Top Views, 120,000 & 150,000

Models: SUF-60-120 SUF-100-250

1 80
Download 80 pages 61 Kb
Page 8
Image 8
Top Views

Top Views

120,000 & 150,000

 

6

7

8

9

Btu/hr MODELS

 

 

 

 

 

 

 

 

10

TOP VIEW

5

2

 

 

11

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

13

3

 

 

 

 

 

2

 

 

 

 

14

 

 

 

 

 

 

 

FRONT

 

15

 

1

 

 

17

16

 

 

 

 

 

Figure 3

SUF 120 & 150 Components

1.Water Heater’s 120 VAC on/off switch.

2.Powered anode rods. The water heater’s covered in this manual are equipped with powered (non sacrificial) anode rod(s). The SUF 120 has one powered anode, all other models will have two. Protective current is fed by the control system to the titanium electrodes at the end of each anode rod. This current flows through the water to the conductive surfaces inside the storage tank which diminishes the corrosive effect (rusting) of water when it comes in contact with steel.

3.Central Control Board (CCB) enclosure. This enclosure houses the control system’s main circuit board. The CCB regulates water temperature and controls all water heater functions, see Control System Operation on page 44.

4.Intake air connection - 3 inch PVC.

5.120 VAC junction box. Incoming power supply and ground connections are made here. See Power Supply on page 14.

6.Water heater's 24 Volt Gas Valve.

7.Supply gas line connection. See the requirements for the

Supply Gas Line on page 14.

8.Low Gas Pressure switch. Normally open contacts that close on a rise in pressure. This switch is used to insure supply gas pressure is above minimum requirements. The control system monitors this switch and will disable heating operation if its contacts are open during a heating cycle. See Table 4 and the Gas Pressure Requirements on page 14.

9.Blocked Intake Air switch. Normally closed contacts that open on fall in pressure. This switch is used to insure intake (combustion) air to the water heater is not restricted. The control system monitors this switch and will disable heating operation if its contacts are open during a heating cycle.

10.Vent connection (exhaust elbow) - 3 inch PVC.

11.Combustion Blower.

12.Blocked Exhaust (vent) switch. Normally closed contacts that open on a rise in pressure. This switch is used to insure the Exhaust (vent) piping connected to the water heater is not restricted. The control system monitors this switch and will disable heating operation if its contacts are open during a heating cycle.

13.Blower Prover switch. Normally open contacts that close on a rise in pressure. This switch is used to insure the Combustion Blower is operating properly. The control system monitors this switch and will disable heating operation if its contacts are closed before the Combustion Blower is energized or open any time during a heating cycle. See Sequence Of

Operation on page 58.

14.Temperature-Pressure Relief Valve. See Temperature- Pressure Relief Valve on page 16.

15.Upper Temperature Probe, 1 of 2 temperature probes. The water heater’s control system monitors this probe to detect water temperature in the upper portion of the storage tank.

The Upper Temperature Probe also houses the ECO (energy cut out) switch. This is a non adjustable high temperature limit switch. The ECO switch contacts are normally closed and will open on a temperature rise. See High Temperature Limit Control (ECO) on page 43.

16.Water outlet connection 1 1/2” NPT.

17.UIM (user interface module). The UIM includes the display circuit board, the control system’s LCD display and operational buttons. Used to adjust various user settings and view operational information. See Control System Operation on page 44.

8

Page 8
Image 8
State Industries SUF-60-120, SUF-100-250 Btu/hr MODELS, Front, Top Views, 120,000 & 150,000, SUF 120 & 150 Components