State Industries SUF-60-120 Explosion Hazard, Powered Anode Rods, Drain Valve and Access Panels

Models: SUF-60-120 SUF-100-250

1 80
Download 80 pages 61 Kb
Page 66
Image 66
UN-LIME® Professional Delimer

TABLE 15

UN-LIME® Professional Delimer

Part Number

Description

9005416105

4 - 1 gallon (case)

9005417105

1 - 5 gallon

Powered Anode Rods

To insure a long, trouble-free operating life, the water heaters covered in this manual are factory equipped with a powered anode system. The anode rods (2) are of a permanent design and do not need replacing unless damaged. Inspection and cleaning should be performed once a year.

Note: Follow the instructions to drain the water heater storage tank on page 64 first. Remove the powered anodes from the water heater by loosening the 3/4" NPT bushing that forms the top of the anodes. Do not disassemble the retaining nut and wire terminal from the top while installed in the water heater, the anode's electrode may fall inside the tank. Remove the entire anode rod from the water heater prior to inspection. Clean the anode rods with a soft cloth and reinstall. Follow the instructions for filling the water heater on page 52 when finished.

Drain Valve and Access Panels

The water heaters covered in this manual are equipped with a drain valve, see Features And Components on page 7 for location. The water heaters covered in this manual are also equipped with a cleanout opening for sediment and lime scale removal. See Figure 63 on page 65.

Temperature-Pressure Relief Valve Test

Part NumberPowered Anode Rods Burn hazard.

Drain Valve and Access Panels Hot water discharge.

Temperature-Pressure Relief Valve Test Keep clear of Temperature- Pressure Relief Valve discharge outlet.

It is recommended that the Temperature-Pressure Relief Valve should be checked to ensure that it is in operating condition every 6 months.

When checking the Temperature-Pressure Relief Valve operation, make sure that (1) no one is in front of or around the outlet of the Temperature-Pressure Relief Valve discharge line, and (2) that the water discharge will not cause any property damage, as the water may be extremely hot. Use care when operating valve as the valve may be hot.

To check the relief valve, lift the lever at the end of the valve several times, see Figure 64. The valve should seat properly and operate freely.

If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater and drain the water heater, see Draining And Flushing on page 64. Replace the Temperature- Pressure Relief Valve with a properly rated/sized new one, see Temperature-Pressure Relief Valve on page 16 for instructions on replacement.

TEMPERATURE-PRESSURE

RELIEF VALVE

DISCHARGE PIPE

Figure 64

If the Temperature-Pressure Relief Valve on the water heater weeps or discharges periodically, this may be due to thermal expansion.

Note: Excessive water pressure is the most common cause of Temperature-Pressure Relief Valve leakage. Excessive water system pressure is most often caused by "thermal expansion" in a "closed system." See Thermal Expansion and Closed Water Systems on page 15. The Temperature-Pressure Relief Valve is not intended for the constant relief of thermal expansion.

Temperature-Pressure Relief Valve leakage due to pressure build up in a closed system that does not have a thermal expansion tank installed is not covered under the limited warranty. Thermal expansion tanks must be installed on all closed water systems.

Do not plug the Temperature-Pressure Relief Valve opening. This can cause property damage, serious injury or death.

Explosion Hazard

Vent System Temperature-Pressure Relief Valve must comply with ANSI Z21.22- CSA 4.4 and ASME code.

Properly sized temperature- pressure relief valve must be installed in opening provided.

Can result in overheating and excessive tank pressure.

Can cause serious injury or death.

Vent System

Examine the vent system once a year. Points of inspection are as follows:

1.Check for obstructions and/or deterioration of the intake air and/or vent piping and the intake air and vent terminations. Replace immediately where needed.

2.The debris screens in the intake air and vent terminations should be should be cleaned of foreign material and soot. See Figure 26 on page 29.

Note: Do not reach inside the vent hood when the heater is in operation.

3.Check all vent system connections for leakage and repair or reseal as necessary.

66

Page 66
Image 66
State Industries SUF-60-120 Explosion Hazard, Powered Anode Rods, Drain Valve and Access Panels, Vent System, Part Number