c.Station bypass switch: For every station, the box labeled Bypass Switch should match the state of the switch at the station. Flip the switches at the stations in order to check that:
1.Each station’s box is black when its bypass switch is in the “0” position (station ready to convey), and
2.Each station’s box is green when its bypass switch is in the “1” position (station bypassed).
Leave each station with its bypass switch off (in the “0” position).
d.Station receiver level: For each station whose receiver has no
1.The box on this screen is green when the sensor indicates that no material is present, and
2.The box is black when the sensor indicates that material is present.
Note: You will not see any alarms for “receiver low level” during this procedure. In order to prevent nuisance alarms when the system starts, the controller’s software is designed to issue these alarms only after material has been detected in the receiver at least once.
When you have finished calibration and checking, reinstall the switch in the receiver.
e.Pump inputs (verify, high vacuum, fault #1, fault #2): All boxes for pump inputs should be black. Because these inputs can turn on only when the pump is running, it is not possible to check their operation further at this point.
If any input does not operate as expected, check the wiring on the ArmorBlock. If this does not solve the problem, phone the Service Department for assistance.