Alarm message

Possible cause

Output power failure

Power flat cable for network is not installed in ArmorBlock base

(Critical)

properly

Pump failure

Circuit breaker or overload protector has tripped.

(Critical)

Contactor has malfunctioned.

Pump fault #1

(Function determined by your facility.)

Pump fault #2

(Function determined by your facility.)

Pump starter output failure

Patch cord for contactor is disconnected.

Patch cord for contactor has been cut.

(Critical)

Contactor coil is defective.

 

Vent solenoid output failure

Patch cord for vent is disconnected.

Patch cord for vent has been cut.

(Critical)

Vent solenoid valve has malfunctioned.

 

System Alarms

Alarm message

Possible cause

Central alarm failure

Patch cord for horn or strobe light is disconnected.

Patch cord for horn or strobe light has been cut.

 

All horns and strobe lights for this central alarm are defective.

 

Power supply for a centralized purge valve is not turned on.

Centralized purge output power

Power supply for a centralized purge is not connected properly.

An ArmorBlock for centralized purge valves is defective.

failure

Base of an ArmorBlock for centralized purge valves is defective.

(Critical)

Power flat cable for network is not properly installed in the base of an

 

 

ArmorBlock for centralized purge valves.

 

Patch cord for a centralized purge valve is disconnected.

 

Patch cord for a centralized purge valve has been cut.

 

Solenoid for a centralized purge valve has malfunctioned.

 

An ArmorBlock for centralized purge valves is defective.

 

Base of an ArmorBlock for centralized purge valves is defective.

Centralized purge valve failure

Network flat cable is not properly installed in the base of an

ArmorBlock for centralized purge valves.

(Critical)

 

Note: Once you have found and corrected the cause of this alarm,

 

enable a station (p. 60) that uses the purge valve for which the alarm

 

occurred. (To identify such a station, go to a Station Operator screen

 

(p. 61) and navigate among the stations (p. 62) until you find a

 

station assigned to this purge valve.) Once the system successfully

 

uses this purge valve, it clears the alarm and enables all other

 

stations that use this valve.

PLC low battery

Battery for the controller is defective.

Battery for the controller is old and drained.

 

Scanner communication failure

Power supply for network is not turned on.

Power supply for network is not connected properly.

(Critical)

Main enclosure is not connected properly.

 

DeviceNet scanner is defective.

Scanner duplicate node

Two nodes (stations, pumps, central alarms, or centralized purge

(Critical)

valves) are assigned the same address.

Scanner incorrect node

The ArmorBlock for a pump has an address for a station.

assignment

The ArmorBlock for a central alarm has an address for a station.

(Critical)

The ArmorBlock for a station has an address for a pump.

7/50D Plus or 7/50D Controller

Chapter 7: Troubleshooting

83

Page 84
Image 84
Sterling Plumbing 882.00254.00 specifications System Alarms