Teledyne API Model 465L O3 Monitor Operation Manual
16 05509F DCN6409
Analog Output, Voltage Mode 0 - 5V
Isolated Analog Output, 4-
20mA Mode Maximum voltage between outputs and ground
60V peak
System OK Status Relay SPDT (Form C) Dry Contact, 250 VAC, 5A
Global Alarm Relays SPDT (Form C) Dry Contact, 250 VAC, 5A (x2,
HI and HI-HI)
Instrument Status Outputs 6 - SPST Dry Contact, 50VDC, 250mA Resistive
Load
Multi-Stream Specifications:
Minimum Stream Duration
(Cycle Time) 1.0 min
Stream Alarm Relays (HI and
HI-HI) SPST Dry Contact, 50VDC, 250mA Resistive
Load (2 per stream)
Stream ID Relays SPST Dry Contact, 50VDC, 250mA Resistive
Load (1 per stream)
2.2. Approvals
This section presents Safety and Electromagnetic Compatibility (EMC) compliance approvals
for the Model 465L monitor.

2.2.1. Safety

IEC 61010-1:2001, Safety requirements for electrical equipment for
measurement, control, and laboratory use.
CE: 2006/95/EC, Low-Voltage Directive
North American:
cNEMKO (Canada): CAN/CSA-C22.2 No. 61010-1-04
NEMKO-CCL (US): UL No. 61010-1 (2nd Edition)

2.2.2. EMC

EN 61326-1 (IEC 61326-1), Class A Emissions/Industrial Immunity
EN 55011 (CISPR 11), Group 1, Class A Emissions
FCC 47 CFR Part 15B, Class A Emissions
CE: 2004/108/EC, Electromagnetic Compatibility Directive