Toshiba G9000 operation manual UPS Installation Environment, Environment standard

Models: G9000

1 104
Download 104 pages 52.29 Kb
Page 14
Image 14

!

WARNING 3

 

NOTE

The UPS is to be installed in a controlled environment.

Improper storage and installation environment may deteriorate insulation, shorten component life and cause malfunctions.

Keep the installation environment per standard described as follows:

TABLE 1.1 UPS Installation Environment

No.

Item

 

Environment standard

1

Installation

Indoors

 

 

 

location

 

 

 

 

 

 

 

2

Ambient

Minimum temperature: 32 °F(0 °C), Maximum temperature: 104 °F(40 °C) The

 

temperature

average temperature over any 24-hour period must be in the range 41 °F (5 °C)

 

 

to 95 °F(35 °C).

 

 

 

 

 

 

3

Relative humidity

The relative humidity must be held between 5 and 95%. There must be no

 

 

condensation due to temperature changes.

 

 

 

 

4

Altitude

This equipment must not be applied at altitude that exceeds 2250m(7380ft)

 

 

above seal level.

 

 

 

 

 

 

5

Dust

Dust in the room where the UPS is installed must not exceed normal

 

 

atmospheric dust levels. In particular, that dust should not include iron particles,

 

 

oils or fats, or organic materials such as silicone.

 

 

 

 

6

Inflammable gas

There should be no inflammable/explosive gas.

 

 

 

 

 

 

following

Hydrogen sulfide (H2S)

 

No more than 0.003 PPM

 

Sulfurous acid gas (SO2)

 

No more than 0.01 PPM

 

IEC654-4

 

 

Chlorine gas (Cl2)

 

No more than 0.002 PPM

 

Part 4

 

 

 

Ammonia gas (NH3)

 

No more than 1 PPM

 

 

Nitrous oxides (NOx)

 

No more than 0.05 PPM

 

 

Ozone (O3)

 

No more than 0.002 PPM

4

G9000 Installation and Operation Manual

Page 14
Image 14
Toshiba G9000 operation manual UPS Installation Environment, Environment standard