The parts (included RemotEyeII) for UPS monitoring are listed below.

TABLE 2-1Parts list for UPS monitoring

Parts No.

Part name

Qt’y

1

PSAU-60* :Power supply PCB (PS1)

1

2

3BBA0083P001 :Cable1

1

3

RemotEyeII module

1

4

D-sub 9-pin to RJ45 Cable:Cable2

1

5

12V Power Cable:Cable3

1

 

* – PCB revision suffix may be applied.

 

 

FIGURE 2.15 PSAU-60 PCB (PS1)

 

Connector CN44

to be connected with CN27 of DPAU-81(SW1).

Connected with 3BBA0083P001(Cable1) Shown in FIGURE 2.17.

FIGURE 2.16 DPAU-81 (SW1)

Connector CN27 to be connected with

CN44 of PSAU-60(PS1).

D-sub connector CN1 to be connected with

RemotEyeII.

Terminal block TN to feed 12VDC power

to RemotEyeII.

(12V across P to N)

Optional interface CN2 to give 12VDC power (12V Pin#1 to #2)

(Note 12VDC exposed)

FIGURE 2.17 3BBA0083P001 (Cable1)

D3200 5pin (housing)

G9000 Installation and Operation Manual

43

Page 53
Image 53
Toshiba G9000 operation manual PSAU-60 PCB PS1