Failure Code List | Table 6.1 Fault Code |
|
|
| |||
|
|
|
|
| |||
Note 3 |
|
|
|
| Note 1 | Note 2 | |
Code | Status message | Meaning | Guidance | Buzzer | External | Failure | |
indication | relay contact | lamp | |||||
|
|
|
| ||||
|
|
|
|
|
|
| |
| AC INPUT VOLTAGE | Input line voltage is out of the specified | CHECK INPUT | Intermittent | Alarm |
| |
UA801 | POWER | AC input | - | ||||
OUT OF RANGE | range. | sound | |||||
| SOURCE | abnormal |
| ||||
|
|
|
|
| |||
|
|
|
|
|
|
| |
| AC INPUT | Input line frequency is out of the specified | CHECK INPUT | Intermittent | Alarm |
| |
UA802 | FREQUENCY OUT | POWER | AC input | - | |||
range. | sound | ||||||
| OF RANGE | SOURCE | abnormal |
| |||
|
|
|
| ||||
|
|
|
|
|
|
| |
| AC INPUT PHASE | Input line power conductors are not wired in | CHECK INPUT | Intermittent | Alarm |
| |
UA803 | POWER | AC input | - | ||||
ROTATION ERROR | a proper phase sequence. | sound | |||||
| SOURCE | abnormal |
| ||||
|
|
|
|
| |||
|
|
|
|
|
|
| |
UA804 | CONVERTER OPE. | The converter interlock is active. | - | Intermittent | Alarm | - | |
PROHIBITED | sound | ||||||
|
|
|
|
| |||
| INVERTER | The output load current has exceeded 105% | WARNING : | Intermittent | Alarm |
| |
UA805 | DECREASE | - | |||||
OVERLOAD | of the rated current. | sound | Overload | ||||
| LOAD |
| |||||
|
|
|
|
|
| ||
| INVERTER | The output load current has exceeded 110% | WARNING : | Intermittent | Alarm |
| |
UA806 | DECREASE | - | |||||
OVERLOAD | of the rated current. | sound | Overload | ||||
| LOAD |
| |||||
|
|
|
|
|
| ||
| INVERTER | The output load current has exceeded 125% | WARNING : | Intermittent | Alarm |
| |
UA807 | DECREASE | - | |||||
OVERLOAD | of the rated current. | sound | Overload | ||||
| LOAD |
| |||||
|
|
|
|
|
| ||
| INVERTER | The output load current has exceeded 150% | WARNING : | Intermittent | Alarm |
| |
UA808 | DECREASE | - | |||||
OVERLOAD | of the rated current. | sound | Overload | ||||
| LOAD |
| |||||
|
|
|
|
|
| ||
| INVERTER | Short time | WARNING : | Intermittent | Alarm |
| |
UA810 | DECREASE | - | |||||
OVERLOAD | during the inverter operation. | sound | Overload | ||||
| LOAD |
| |||||
|
|
|
|
|
| ||
| BYPASS VOLTAGE | Bypass line voltage is out of the specified | CHECK BYPASS | Intermittent | Alarm |
| |
UA812 | Bypass input | - | |||||
OUT OF RANGE | range. | INPUT | sound | ||||
| abnormal |
| |||||
|
|
|
|
|
| ||
| BYPASS PHASE | Bypass line power conductors are not wired | CHECK BYPASS | Intermittent | Alarm |
| |
UA813 | Bypass input | - | |||||
ROTATION ERROR | in a proper phase sequence. | INPUT | sound | ||||
| abnormal |
| |||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
| BYPASS | Bypass line frequency is out of the specified | CHECK BYPASS | Intermittent | Alarm |
| |
UA814 | FREQUENCY OUT | Bypass input | - | ||||
range. | INPUT | sound | |||||
| OF RANGE | abnormal |
| ||||
|
|
|
|
| |||
|
|
|
|
|
|
| |
UA815 | TRANSFER | Transfer to the bypass is not available due to | - | Intermittent | Alarm | - | |
PROHIBITED | bypass abnormality. | sound | |||||
|
|
|
| ||||
UA817 | EMERGENCY STOP | The emergency stop was activated by the | - | - | Alarm | - | |
ACTIVATED | EPO switch or an external contact. | ||||||
|
|
|
|
| |||
| TRANSFER | The UPS could not transfer to the bypass |
|
|
|
| |
UA821 | because the inverter output was not | - | - | Alarm | - | ||
PROHIBITED | |||||||
| synchronized to the bypass. |
|
|
|
| ||
|
|
|
|
|
| ||
| TRANSFER | The UPS could not transfer to the bypass |
|
|
|
| |
UA822 | because external “generator operation” | - | - | Alarm | - | ||
PROHIBITED | signal indicates a backup generator is in | ||||||
|
|
|
|
| |||
|
| operation. |
|
|
|
|
G9000 Installation and Operation Manual | 77 |