WARNING 4

NOTE

This UPS does not include a Bypass input circuit breaker (MCCB) to protect the bypass circuit. The Bypass input circuit breaker (MCCB) is to be field supplied and installed. Recommended Breaker (MCCB)'s Specifications are as follows:

TABLE 1.2 Rating of Bypass Input Circuit Breaker

Capacity (kVA)

Bypass Voltage (Vac)

Bypass Rating (Aac)

Breaker (A)

80

480

96

125

 

 

 

 

100

480

120

150

 

 

 

 

160

480

192

250

 

 

 

 

225

480

271

350

 

 

 

 

300

480

361

500

 

 

 

 

500

480

601

800

 

 

 

 

750

480

902

1200

 

 

 

 

AC input and AC output overcurrent protection and disconnect devices shall be field supplied and installed. The DC circuit breaker (MCCB) shall be field supplied and installed. The overcurrent protection device should be installed in the Battery cabinet and rated as indicated in TABLE 1.6.

Note: The DC input overcurrent protection (Battery disconnect breaker) hereinafter will be referred as “CB2”.

G9000 Installation and Operation Manual

5