Toshiba G9000 operation manual Terminals 9 to 10 Remote Inverter Stop input terminal IN2

Models: G9000

1 104
Download 104 pages 52.29 Kb
Page 48
Image 48

Details of input contacts for remote access : TN1

Terminals 7 to 8 Remote "Inverter Start" input terminal (IN1)

Used to start inverter from a remote location. UPS must be programmed for remote operation. Refer to Operations Menu for procedure.

Terminals 9 to 10 Remote "Inverter Stop" input terminal (IN2)

Used to stop inverter from a remote location. UPS must be programmed for remote operation. Refer to Operations Menu for procedure.

Terminals 11 to 12 "Battery Temp. High" contact input (IN3)

Input fed by a thermocouple that monitors battery temperature. The converter float voltage level is reduced for battery over-temperature conditions. External thermocouple is user supplied

Terminals 13 to 14 "Power Demand” Command contact input (IN4)

This contact is used to control the input power. Power demand is turned ON when the contact is closed, and power demand is turned OFF when the contact is open. (The Power demand function is custom designed by the factory to match the users specific system specifications. Contact the factory for additional information.)

Terminals 15 to 16 "Remote EPO" contact input

Used to perform a remote UPS Emergency Power Off (EPO).

The load will be dropped.

!The above items are the default settings.

Contact Toshiba International Corporation for setup information.The UPS is equipped with a selectable input contact item.

NOTE

In all cases, a switch having a protective cover is recommended in order to reduce the possibility of accidental operation.

CAUTION

38

G9000 Installation and Operation Manual

Page 48
Image 48