Toshiba G9000 operation manual Inverter Call Service

Models: G9000

1 104
Download 104 pages 52.29 Kb
Page 91
Image 91

Note 3

 

 

 

 

Note 1

 

Note 2

 

 

 

 

 

 

 

Code

Status message

Meaning

Guidance

Buzzer

External

 

Failure

 

indication

relay contact

 

lamp

 

 

 

 

 

 

 

UF301

UPS CONTROL

AD reference has an abnormal value.

CALL SERVICE

Continuous

Major

 

Lit on

CIRCUIT ERROR

ENGINEER

sound

 

 

 

 

 

 

 

UF302

UPS CONTROL

Detection of an external interruption during

CALL SERVICE

Continuous

Major

 

Lit on

CIRCUIT ERROR

the software execution.

ENGINEER

sound

 

 

 

 

 

 

UF303

UPS CONTROL

Timer does not reset in the specified period

CALL SERVICE

Continuous

Major

 

Lit on

CIRCUIT ERROR

(WDT settings)

ENGINEER

sound

 

 

 

 

 

 

UF305

UPS CONTROL

Detection of an abnormal clock speed in the

CALL SERVICE

Continuous

Major

 

Lit on

CIRCUIT ERROR

DSP or FPGA.

ENGINEER

sound

 

 

 

 

 

 

UF306

UPS CONTROL

Control power supply voltage is below the

CALL SERVICE

Continuous

Major

 

Lit on

CIRCUIT ERROR

specified level.

ENGINEER

sound

 

 

 

 

 

 

 

INVERTER

 

CALL SERVICE

Continuous

 

 

 

 

UF309

VOLTAGE

Inverter voltage is out of the specified range.

Major

 

Lit on

ENGINEER

sound

 

 

ABNORMAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL POWER

MMS backup control power supplies exhibit

CALL SERVICE

Continuous

 

 

 

 

UF310

SUPPLY

Major

 

Lit on

abnormal condition.

ENGINEER

sound

 

 

ABNORMAL

 

 

 

 

 

 

 

 

 

 

 

 

UF320

UPS CONTROL

Cable disconnection in the parallel interface

CALL SERVICE

Continuous

Major

 

Lit on

CIRCUIT ERROR

board during load supply.

ENGINEER

sound

 

 

 

 

 

 

UF323

UPS CONTROL

Major communication error during parallel

CALL SERVICE

Continuous

Major

 

Lit on

CIRCUIT ERROR

operation.

ENGINEER

sound

 

 

 

 

 

 

UF331

UPS CONTROL

Gate driver abnormal for phase U (Note 4)

CALL SERVICE

Continuous

Major

 

Lit on

CIRCUIT ERROR

ENGINEER

sound

 

 

 

 

 

 

 

UF332

UPS CONTROL

Gate driver abnormal for phase V (Note 4)

CALL SERVICE

Continuous

Major

 

Lit on

CIRCUIT ERROR

ENGINEER

sound

 

 

 

 

 

 

 

UF333

UPS CONTROL

Gate driver abnormal for phase W (Note 4)

CALL SERVICE

Continuous

Major

 

Lit on

CIRCUIT ERROR

ENGINEER

sound

 

 

 

 

 

 

 

UF334

UPS CONTROL

Gate driver abnormal for chopper (Note 4)

CALL SERVICE

Continuous

Major

 

Lit on

CIRCUIT ERROR

ENGINEER

sound

 

 

 

 

 

 

 

 

CONTROL POWER

SMS backup control power supplies exhibit

CALL SERVICE

Intermittent

 

 

 

 

UF352

SUPPLY

Minor

 

Flicker

abnormal.

ENGINEER

sound

 

 

ABNORMAL

 

 

 

 

 

 

 

 

 

 

 

 

UF363

UPS CONTROL

Synchronization error signal is being

CALL SERVICE

Intermittent

Minor

 

Flicker

CIRCUIT ERROR

received for a considerable time.

ENGINEER

sound

 

 

 

 

 

 

UF371

UPS CONTROL

Minor communication error during parallel

CALL SERVICE

Intermittent

Minor

 

Flicker

CIRCUIT ERROR

operation.

ENGINEER

sound

 

 

 

 

 

 

 

UPS CONTROL

Unable to synchronize the inverter output

CALL SERVICE

Intermittent

 

 

 

 

UF372

and the bypass voltage when the bypass is

Minor

 

Flicker

CIRCUIT ERROR

ENGINEER

sound

 

 

normal.

 

 

 

 

 

 

 

 

 

 

 

 

UF374

UPS CONTROL

Cable disconnection in the parallel interface

CALL SERVICE

Intermittent

Minor

 

Flicker

CIRCUIT ERROR

board.

ENGINEER

sound

 

 

 

 

 

 

UF375

UPS CONTROL

Unable to achieve synchronization for

CALL SERVICE

Intermittent

Minor

 

Flicker

CIRCUIT ERROR

parallel operation.

ENGINEER

sound

 

 

 

 

 

 

UF376

UPS CONTROL

No control response from another UPS

CALL SERVICE

Intermittent

Minor

 

Flicker

CIRCUIT ERROR

although its detection is possible.

ENGINEER

sound

 

 

 

 

 

 

UF377

UPS CONTROL

Overload detection signal is being received

CALL SERVICE

Intermittent

Minor

 

Flicker

CIRCUIT ERROR

continuously for a considerable time.

ENGINEER

sound

 

 

 

 

 

 

UF378

UPS CONTROL

No answer for sending synchronizing signal.

CALL SERVICE

Intermittent

Minor

 

Flicker

CIRCUIT ERROR

ENGINEER

sound

 

 

 

 

 

 

 

UF379

UPS CONTROL

Abnormal clock speed of the parallel control

CALL SERVICE

Intermittent

Minor

 

Flicker

CIRCUIT ERROR

board processor.

ENGINEER

sound

 

 

 

 

 

 

G9000 Installation and Operation Manual

81

Page 91
Image 91
Toshiba G9000 operation manual Inverter Call Service