!The above alarms are the default settings.

Contact Toshiba International Corporation for setup information.The UPS is equipped with a selectable output contact feature.

NOTE

B)Input Contacts (for remote access of UPS)

External contacts are provided by the user of the UPS system. Terminal voltage at the UPS is 24VDC. Provide external dry contact accordingly.

Do not apply voltages to remote access input terminals.

Damage to UPS may result.

PROHIBIT

Refer to Figure 2.12 for a typical wiring configuration. Although this figure applies to the remote start/stop terminals, the same wiring arrangement is used for emergency stop; power demand; and battery temperature high.

FIGURE 2.12 Remote "Start" Contact Connections

UPS Cabinet

Relay

Coil

24 VDC

Relay Coil current : 8.3mA

External to UPS Cabinet

Start

Start

Switch

Common

0.5S- 4S

ON

OFF

Use Momentary Switches Only

User supplied

G9000 Installation and Operation Manual

37

Page 47
Image 47
Toshiba G9000 operation manual Input Contacts for remote access of UPS, Remote Start Contact Connections