Toshiba G9000 operation manual 52S Abnormal

Models: G9000

1 104
Download 104 pages 52.29 Kb
Page 92
Image 92

 

Note 3

 

 

 

 

 

Note 1

 

Note 2

 

Code

 

Status message

Meaning

Guidance

Buzzer

 

External

 

 

Failure

 

 

indication

 

 

relay contact

 

 

lamp

 

 

 

 

 

 

 

 

 

 

 

 

UF401

52S ABNORMAL

Error to close the contactor 52S.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF402

52S ABNORMAL

Error to open the contactor 52S.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF420

52L OPERATION

Load circuit breaker 52L opened during

CHECK 52L

Continuous

 

Major

 

Lit on

 

ERROR

inverter operation.

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF451

52S ABNORMAL

Contactor 52S failed during load transfer

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

from inverter to bypass.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF452

CB3 ABNORMAL

Contactor CB3 is not working properly.

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Note 1) 1)

"Major" is defined as major failure. Inverter transferred to the static bypass line;

 

 

 

2)"Minor" is defined as a minor failure. UPS continues to operate normally, but cause of alarm must be identified;

(Note 2) Indicates one of two possible LED illumination patterns - continuously on (lit) or intermittent (flicker).

(Note 3) Code indication means:

 

UA+++------------------------

Alarm

UF+++------------------------

Failure

U%0++ -----------------------

Rectifier circuit failure

U%1++ -----------------------

DC circuit failure

U%2++ -----------------------

Inverter circuit failure

U%3++ -----------------------

Control circuit failure

U%4++ -----------------------

Bypass system failure

U%8++ -----------------------

Alarm

U%+00 - U%+49 ---------

Major failure

U%+50 - U%+99 ---------

Minor failure

*)

“+” denotes any numeral from 0 to 9

*)

“%” denotes either “A” or “F”

82

G9000 Installation and Operation Manual

Page 92
Image 92
Toshiba G9000 operation manual 52S Abnormal