Toshiba G9000 External Battery Supply, UPS Capacity DC Voltage, KVA Rating Current Permitted a

Models: G9000

1 104
Download 104 pages 52.29 Kb
Page 56
Image 56

D)External Battery Supply

Please refer to the following when installing and maintaining batteries:

1. The customer shall refer to the battery manufacturer's installation manual for

!

battery installation and maintenance instructions.

 

 

2. The maximum permitted fault current from the remote battery supply, and the

 

DC voltage rating of the battery supply over-current protective device are

NOTE

shown in Table 3.3.

 

 

 

 

TABLE 3.3 Maximum Permitted Fault Current

UPS Capacity

 

DC Voltage

Maximum Fault

 

 

(kVA)

 

Rating (V)

Current Permitted (A)

 

 

 

 

 

 

 

 

80

 

480

25,000

 

 

 

 

 

 

 

 

100

 

480

25,000

 

 

 

 

 

 

 

 

160

 

480

25,000

 

 

 

 

 

 

 

 

225

 

480

25,000

 

 

 

 

 

 

 

 

300

 

480

25,000

 

 

 

 

 

 

 

 

500

 

480

25,000

 

 

 

 

 

 

 

 

750

 

480

25,000

 

 

 

 

 

 

 

3.3PROCEDURE FOR CABLE CONNECTIONS

1.Confirm the capacity of the UPS being installed. Identify the input/output power terminal blocks accordingly as shown in the Figures 3.1 through 3.5.

2.Connect the internal control wire and power wire.

(1)Control wire Inter-connect

1.CB2 UVR to terminal TN1-1, 2 of external I/F PCB IOAU-09.

2.CB2 ON Auxiliary to terminal TN1-3, 4 of external I/F PCB IOAU-09.

(2)Power wire (AC input, Bypass input, AC output) Inter-connect

a.) From user’s distribution panel

1.X1 (A-phase) to A bus bar in UPS

2.X2 (B-phase) to B bus bar in UPS

3.X3 (C-phase) to C bus bar in UPS b.) DC Input to UPS

1.Positive cable to BP bus bar in UPS

2.Negative cable to BN bus bar in UPS

46

G9000 Installation and Operation Manual

Page 56
Image 56
Toshiba G9000 operation manual External Battery Supply, UPS Capacity DC Voltage, KVA Rating Current Permitted a