| Note 3 |
|
|
|
|
| Note 1 |
| Note 2 | |||
|
|
|
| |||||||||
| Code |
| Status message | Meaning | Guidance | Buzzer |
| External |
|
| Failure |
|
| indication |
|
| relay contact |
|
| lamp |
| ||||
|
|
|
|
|
|
|
|
|
| |||
| UF201 | INVERTER | Detection of output overvoltage. | CALL SERVICE | Continuous |
| Major |
| Lit on | |||
| OVERVOLTAGE | ENGINEER | sound |
|
| |||||||
|
|
|
|
|
|
|
|
|
| |||
| UF202 | INVERTER | Output voltage dropped.below specs. | CALL SERVICE | Continuous |
| Major |
| Lit on | |||
| UNDERVOLTAGE | ENGINEER | sound |
|
| |||||||
|
|
|
|
|
|
|
|
|
| |||
| UF203 | INVERTER | Detection of inverter overcurrent. | CALL SERVICE | Continuous |
| Major |
| Lit on | |||
| OVERCURRENT | ENGINEER | sound |
|
| |||||||
|
|
|
|
|
|
|
|
|
| |||
|
|
| OUTPUT CIRCUIT | Detection of a large variation of the reference | CALL SERVICE | Continuous |
|
|
|
|
|
|
| UF204 | error signal (current reference and actual |
| Major |
| Lit on | ||||||
| ABNORMAL | ENGINEER | sound |
|
| |||||||
|
|
| current). |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| |
| UF206 | UPS CONTROL | Discrepancy between output voltage and | CALL SERVICE | Continuous |
| Major |
| Lit on | |||
| CIRCUIT ERROR | external voltage (bypass, common ac bus) | ENGINEER | sound |
|
| ||||||
|
|
|
|
|
|
|
|
| ||||
| UF207 | ZERO PHASE | Inverter | CALL SERVICE | Continuous |
| Major |
| Lit on | |||
| OVERCURRENT | ENGINEER | sound |
|
| |||||||
|
|
|
|
|
|
|
|
|
| |||
| UF208 | UPS CONTROL | Cross current is abnormal. | CALL SERVICE | Continuous |
| Major |
| Lit on | |||
| CIRCUIT ERROR | ENGINEER | sound |
|
| |||||||
|
|
|
|
|
|
|
|
|
| |||
| UF209 | 52C ABNORMAL | Error to close the contactor 52C. | CALL SERVICE | Continuous |
| Major |
| Lit on | |||
| ENGINEER | sound |
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| ||
| UF210 | 52C ABNORMAL | Error to open the contactor 52C. | CALL SERVICE | Continuous |
| Major |
| Lit on | |||
| ENGINEER | sound |
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| ||
| UF211 | 52C ABNORMAL | No answer from contactor 52C during | CALL SERVICE | Continuous |
| Major |
| Lit on | |||
| inverter operation. | ENGINEER | sound |
|
| |||||||
|
|
|
|
|
|
|
|
|
| |||
| UF213 | OVERTEMP | Heatsinks temperature exceeds thermal | CALL SERVICE | Continuous |
| Major |
| Lit on | |||
| settings. | ENGINEER | sound |
|
| |||||||
|
|
|
|
|
|
|
|
|
| |||
| UF214 | COOLING FAN | Thermal relay activated protection. | CALL SERVICE | Continuous |
| Major |
| Lit on | |||
| ABNORMAL | ENGINEER | sound |
|
| |||||||
|
|
|
|
|
|
|
|
|
| |||
| UF217 | INVERTER | Detection of inverter output phase | CALL SERVICE | Continuous |
| Major |
| Lit on | |||
| OVERVOLTAGE | overvoltage. | ENGINEER | sound |
|
| ||||||
|
|
|
|
|
|
|
|
| ||||
| UF230 | ZERO PHASE | Detection of | CALL SERVICE | Continuous |
| Major |
| Lit on | |||
| OVERCURRENT | ENGINEER | sound |
|
| |||||||
|
|
|
|
|
|
|
|
|
| |||
|
|
| UPS CONTROL | Discrepancy between output voltage and | CALL SERVICE | Intermittent |
|
|
|
|
|
|
| UF253 | inverter voltage, or between output voltage |
| Minor |
| Flicker | ||||||
| CIRCUIT ERROR | ENGINEER | sound |
|
| |||||||
|
|
| and bypass voltage. |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| |
| UF256 | OUTPUT VOLTAGE | Output voltage is outside of the specified | CALL SERVICE | Intermittent |
| Minor |
| Flicker | |||
| ABNORMAL | range. | ENGINEER | sound |
|
| ||||||
|
|
|
|
|
|
|
|
| ||||
| UF257 | 52C ABNORMAL | Contactor 52C failed to open during load | CALL SERVICE | Intermittent |
| Minor |
| Flicker | |||
| transfer from inverter to bypass. | ENGINEER | sound |
|
| |||||||
|
|
|
|
|
|
|
|
|
| |||
| UF258 | LOAD ABNORMAL | Load transfer due to overload for over 4 | CALL SERVICE | Intermittent |
| Minor |
| Flicker | |||
| times within 5 minutes. | ENGINEER | sound |
|
| |||||||
|
|
|
|
|
|
|
|
|
| |||
| UF259 | ANOTHER UPS | No detection of another UPS voltage signal. | CALL SERVICE | Intermittent |
| Minor |
| Flicker | |||
| ABNORMAL | ENGINEER | sound |
|
| |||||||
|
|
|
|
|
|
|
|
|
|
80 | G9000 Installation and Operation Manual |