Code

 

Status message

Meaning

Guidance

Buzzer

 

External

 

 

Failure

 

 

indication

 

 

relay contact

 

 

lamp

 

 

 

 

 

 

 

 

 

 

 

 

UF201

INVERTER

Detection of output overvoltage.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

OVERVOLTAGE

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF202

INVERTER

Output voltage dropped.below specs.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

UNDERVOLTAGE

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF203

INVERTER

Detection of inverter overcurrent.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

OVERCURRENT

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUT CIRCUIT

Detection of a large variation of the reference

CALL SERVICE

Continuous

 

 

 

 

 

 

 

UF204

error signal (current reference and actual

 

Major

 

Lit on

 

ABNORMAL

ENGINEER

sound

 

 

 

 

 

current).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF206

UPS CONTROL

Discrepancy between output voltage and

CALL SERVICE

Continuous

 

Major

 

Lit on

 

CIRCUIT ERROR

external voltage (bypass, common ac bus)

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

UF207

ZERO PHASE

Inverter zero-sequence overcurrent.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

OVERCURRENT

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF208

UPS CONTROL

Cross current is abnormal.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

CIRCUIT ERROR

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF209

52C ABNORMAL

Error to close the contactor 52C.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF210

52C ABNORMAL

Error to open the contactor 52C.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF211

52C ABNORMAL

No answer from contactor 52C during

CALL SERVICE

Continuous

 

Major

 

Lit on

 

inverter operation.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF213

OVERTEMP

Heatsinks temperature exceeds thermal

CALL SERVICE

Continuous

 

Major

 

Lit on

 

settings.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF214

COOLING FAN

Thermal relay activated protection.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

ABNORMAL

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF217

INVERTER

Detection of inverter output phase

CALL SERVICE

Continuous

 

Major

 

Lit on

 

OVERVOLTAGE

overvoltage.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

UF230

ZERO PHASE

Detection of zero-sequence overcurrent.

CALL SERVICE

Continuous

 

Major

 

Lit on

 

OVERCURRENT

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS CONTROL

Discrepancy between output voltage and

CALL SERVICE

Intermittent

 

 

 

 

 

 

 

UF253

inverter voltage, or between output voltage

 

Minor

 

Flicker

 

CIRCUIT ERROR

ENGINEER

sound

 

 

 

 

 

and bypass voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF256

OUTPUT VOLTAGE

Output voltage is outside of the specified

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

ABNORMAL

range.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

UF257

52C ABNORMAL

Contactor 52C failed to open during load

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

transfer from inverter to bypass.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF258

LOAD ABNORMAL

Load transfer due to overload for over 4

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

times within 5 minutes.

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 

 

UF259

ANOTHER UPS

No detection of another UPS voltage signal.

CALL SERVICE

Intermittent

 

Minor

 

Flicker

 

ABNORMAL

ENGINEER

sound

 

 

 

 

 

 

 

 

 

 

 

 