Toshiba G9000 51.2 x 32.7 x 1230 189 31,659, 312 376 500 AT 250 kcmil 2 x 300 kcmil

Models: G9000

1 104
Download 104 pages 52.29 Kb
Page 99
Image 99

Installation Planning Guide for 300kVA UPS

Standard System: 480V Input, 480V Output

General Mechanical Information

Dimensions

Weight

Floor

 

Approximate Full-Load

 

Mechanical Clearance (Inches)from UPS

 

 

Heat Rejection

 

for Ventilation and Maintenance Access

 

(W x D x H)

Loading

 

 

 

 

 

 

 

 

 

 

 

 

Inches

Lbs.

Lbs./ft. 2

 

Btu/Hr

 

Top

Front

Bottom

Sides**

Back

51.2” x 32.7” x 80.7”*

1230

189

31,659

 

20”

40”

0”

0”

0”

*Height includes removable fan housing – Frame height is 78.7”.

**0” clearance for peripheral equipment, 1” clearance for walls.

Primary AC Input (480V 3-Phase / 3-Wire)

 

Maximum Input Power Demand

 

 

Suggested External

 

External Feeder Wire Size: Min. – Max. Per Phase

 

Normal Mode (Recharge Mode)

 

 

Overcurrent Protection

 

 

 

 

 

 

 

kVA

PF

Amps

 

 

Amps

 

AWG or kcmil at 75º C Temp. Rating

 

312 (337)

>0.99

376 (406)

 

 

500 AT

 

(2) x 250 kcmil - (2) x 300 kcmil

Alternate (Bypass) AC Input (480V 3-Phase / 3-Wire)

Maximum Input Power Demand

 

Suggested External

 

 

External Feeder Wire Size:

 

 

Overcurrent Protection

 

 

Min. – Max. Per Phase

 

 

 

 

 

 

 

 

kVA

PF

Amps (Max.)

 

Amps

 

 

AWG or kcmil at 75º C Temp. Rating

 

300

1.0

361

 

500 AT

 

 

(2) x 4/0 - (2) x 250 kcmil

 

Battery Input (480VDC Nominal)

 

Battery Capacity Required

 

 

Discharge at Full

 

Suggested External Overcurrent Protection

External Feeder Wire Size:

 

for Full Load Output

 

 

Load Output

 

 

 

 

 

 

 

 

kWB

 

 

Amps DC

 

Amps

AWG or kcmil at 75º C Temp. Rating

 

309 @ 1.0 PF

 

772

 

800 AT

(2) x 400 kcmil

* Contact factory rep for alternate configurations.

AC Output (480V 3-Phase / 3-Wire)

Rated Output Power

 

Suggested External

 

 

External Feeder Wire Size:

 

 

Overcurrent Protection

 

 

Min. – Max. Per Phase

 

 

 

 

 

 

 

 

kVA

PF

Amps

 

Amps

 

 

AWG or kcmil at 75º C Temp. Rating

 

300

1.0

361

 

500 AT

 

 

(2) x 4/0 – (2) x 250 kcmil

 

Important Notes:

1.Maximum input current is limited to 106% of the full-load input current.

2.Output load conductors are to be installed in separate conduit from input conductors.

3.Control wires and power wires are to be installed in separate conduits.

4.Recommended AC input and output overcurrent protection based on continuous full load current per NEC.

5.Wiring shall comply with all applicable national and local electrical codes.

6.Grounding conductors to be sized per NEC Article 250-122. Neutral conductors to be sized per NEC Article 310.15.

-Primary AC Input: 3φ, 3-wire + ground.

-Alternate AC Input: 3φ, 3-wire + ground.

-AC Output: 3φ, 3-wire + ground.

- DC Input: 2-wire (Positive/Negative) + ground.

7.Nominal battery voltage based on the use of VRLA type batteries (2.0 volts/cell nominal).

8.Maximum battery discharge current based on lowest permissible discharge voltage of 1.67 VPC.

9.DC wires should be sized to allow not more than a 2-volt drop at maximum discharge current.

10.Weights do not include batteries or other auxiliary equipment external to the UPS.

11.Cable sizing calculations based on the following assumptions:

-Minimum size is smallest size based on ampacity at 30 °C.

-Maximum size cable is based on cable bend radius limitations at the UPS terminals.

-Not more than 3 current-carrying conductors installed in conduit in ambient temperature of 30 °C.

-Temperature rating of copper conductors/terminals: 75 °C.

-Reference: 2005 NEC Handbook, Table 310.16.

NOTE: Consult latest edition of applicable national and local codes for possible variations.

12.Ratings of wires and overcurrent devices are suggested minimums. Consult with a registered Professional Engineer within your local area for proper size selections.

TOSHIBA INTERNATIONAL CORPORATION

13131 West Little York Road

Houston, TX 77041

Telephone: (800) 231-1412

Fax: (713) 896-5212

Web Site: www.toshiba.com/ind

G9000 Installation and Operation Manual

89

Page 99
Image 99
Toshiba G9000 51.2 x 32.7 x 1230 189 31,659, 312 376 500 AT 250 kcmil 2 x 300 kcmil, 300 361 500 AT 4/0 2 x 250 kcmil