Rated Output kVA

80

 

100

 

160

 

225

 

300

 

500

 

750

Batt. Capacity Required

75 kWB

 

94 kWB

 

149 kWB

 

210 kWB

 

311 kWB

 

518 kWB

 

776 kWB

at Full Load Output

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of Cells

 

 

 

 

 

 

240

 

 

 

 

 

 

AC OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuration

 

 

 

 

 

 

3 phase, 3 wire

 

 

 

 

 

Voltage

 

 

 

 

 

 

480 V

 

 

 

 

 

Voltage Regulation

 

 

 

±1% (0 – 100% balanced load); ±2% (0 – 100% unbalanced load)

 

Voltage Adj. Range

 

 

 

 

± 5.0% (in 0.5 V increments)

 

 

 

 

Voltage Unbalance

 

 

 

 

2% maximum at 100% unbalanced load

 

 

 

 

THD (VOUT)

 

 

 

< 2% THD at 100% linear load; < 5% THD at 100% nonlinear load

 

Crest Factor

 

 

 

 

 

2.3

 

 

 

 

 

 

Transient Response

 

 

±2% maximum at 100% load step; ±1% maximum at loss/return of AC power;

 

 

 

 

 

 

±5% maximum at load transfer to/from static bypass

 

Transient Recovery Time

 

 

 

 

 

 

Less than 20ms

 

 

 

 

 

Frequency

 

 

 

 

 

 

60 Hz

 

 

 

 

 

Frequency Synch. Range

 

 

 

 

±1% to ± 5% (selectable in 1% increments)

 

 

 

 

Frequency Slew Rate

 

 

 

 

1 Hz/s to 5 Hz/s (selectable in 1 Hz/s increments)

 

Frequency Regulation

 

 

 

 

±0.01% in free running mode

 

 

 

 

Phase Displacement

 

 

 

±1° @ 100% Balanced Load, ±3° @ 100% Unbalanced Load

 

Output Current

96 A

 

120 A

 

192 A

 

271 A

 

361 A

 

601 A

 

902 A

Power Factor

0.9 (0.9

Lagging to 0.95 Leading within output kW rating)

 

 

 

Unity

 

 

Overload Capacity

 

125% for 2 minutes; 150% for 60 seconds

 

125% for 10 minutes; 150% for 60 seconds

Withstand Rating

 

 

65,000 A (with optional fuses)

 

100,000 A (with optional fuses)

ENVIRONMENTAL

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

Forced Air

 

 

 

 

 

Operating Temperature

 

 

32 °F to 104 °F (0 °C to 40 °C). Recommended : 68F to 86F ( 20 °C to 30 °C)

 

Relative Humidity

 

 

 

 

 

5% – 95% Non Condensing

 

 

 

 

Altitude

 

 

 

 

0 to 7380 feet No Derating at 40C

 

 

 

 

Location

 

 

 

 

Indoor (free from corrosive gases and dust)

 

 

 

 

Paint Color

 

 

 

 

 

Munsell N1.5 (Black)

 

 

 

 

 

Clearance Required

 

 

Top: 20 in. (508 mm)

 

 

 

 

Top: 23.6 in. (600 mm)

 

 

 

 

Front: 40 in. (1016 mm)

 

 

 

 

Front: 42.3 in. (1075 mm)

 

 

 

 

Rear: 0 in. (0 mm)

 

 

 

 

 

Rear: 0 in. (0 mm)

 

 

Sides: 0 in. (0 mm) if sidecars used, 1 in. (25 mm) if no sidecars used.

 

Sides: 0 in. (0 mm) if sidecars used, 1 in. (25 mm) if

G9000 Installation and Operation Manual