7-2-1. Louver Control

7-2-1. Louver Control

(1)By pushing the SET button of the remote control during the operation, the louver can be set to the desired position.

And the louver position is stored in the microcom- puter, the louvers will be set to the position au- tomatically at the next operation.

(2)When the AUTO button is pushed, the louver ver- tically swings within range of 25deg.

7-3. DRY Operation

(MODE of the remote control : DRY)

(1)Compressor, outdoor fan and operation display are controlled as shown in Fig. 7-3-1.

temp.)

+3

ON:6min.

OFF:4min.

 

 

temp.– Set

ON:5min.

OFF:5min.

 

 

+2

ON

ON

(Room

 

 

+1

OFF

 

 

 

 

 

 

 

 

Set

 

0

 

 

 

 

 

Compressor fanOutdoor (RY01)

relayCommon (RY02)

OPERATION display

temp.

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 7-3-1

The microprocessor turns the compressor on and off at regular intervals (4 to 6 minutes on and/or off). During the compressor off, the indoor fan will operate in the super low position.

The indoor fan will operate in the AUTO position.

(2)The pattern of operation depending on the relation between room temperature and set temperature is shown below:

Room temp.

Set temp.+1

Set temp.

Compressor

ON

ON

 

ON

 

ON

 

 

 

 

 

 

 

Outdoor fan

 

OFF

 

OFF

OFF

 

 

 

Indoor fan

 

 

 

 

 

 

L.

*S.L.

L.

S.L.

L.

S.L.

L.

 

*Super Low

 

 

 

 

 

Fig. 7-3-2