8-2. Installation Diagram of Indoor and Outdoor Units

For installation of the indoor unit, use the paper pattern on the back.

 

 

3 Clip anchor

more

 

 

 

or

 

 

 

 

 

 

 

 

 

 

Hook

 

Front cabinet

120

mm

 

66mm

Hook

or

 

 

 

 

 

 

 

 

Front panel

 

 

more

 

1 Installation

 

 

 

 

 

 

 

 

plate

 

 

 

 

Hook

120

 

 

 

 

or mm

 

 

 

 

 

 

 

 

 

 

more

 

 

 

 

8

Mounting screw

For the rear and left piping

Wall

Insert the remote control holder cushion between the indoor unit and wall, and lift indoor unit to make work easier.

Do not allow the drain hose to get slack.

Air

filter

 

(Attach

 

 

 

 

to

the

 

 

 

11

back

 

 

Filter

 

side.

 

 

 

 

 

 

 

 

frame

 

 

)

(Attach

 

 

 

 

 

 

 

9Deodorizing filter

6 Pan head wood screw

to

 

 

the

back

 

 

side.

 

 

 

 

)

 

 

 

4 Remote control

10 Purifying

2 Wireless

holder

 

 

filter

 

remote

moreor

 

 

 

control

 

 

 

 

 

 

 

 

mm

or

 

 

 

 

more

 

 

 

600

mm

100

mm

 

45

 

 

or

 

 

 

 

 

 

 

 

 

Before install the wireless

 

more

 

 

 

 

 

 

remote control

With the remote control cover open, load the batteries supplied correctly, observing their polarity.

2 Wireless remote control

7 Batteries

ormore mm 400

Electric parts cover

5 Shield pipe

Extension drain hose (Option:

RB-821SW)

600

mm

 

 

or

 

more

Cut the piping hole sloped slightly

Make sure to run the drain hose sloped downward.

The auxiliary piping can be connected the left, rear left, rear, right or bottom.

Right

Rear

Rear left

BottomLeft

Insulation of refrigerant pipes insulates the pipes separately, not together.

Cover

Loop the connective cable

(about 100 mm in diameter and 300~350 mm long).

6 mm thick heat resisting polyethylene foam

– 20 –

Page 20
Image 20
Toshiba RAS-10SKX, RAS-10SAX, RAS-10SK-E, RAS-10SA-E service manual Installation Diagram of Indoor and Outdoor Units, Attach