9-3-4. Only Compressor does not Operate

Shut off the power supply from AC outlet once and turn it on after 5 seconds.

NO

Does the OPERATION lamp flash?

 

YES

 

Does the power turn on by

NO

pushing the [START/STOP] button

 

 

of the remote control?

 

 

YES

 

 

 

 

 

NO

Is the voltage across the indoor terminal

( 1 - 2 ) 220/230/240 VAC?

 

 

YES

 

 

 

 

 

NO

Is cable connection between indoor

and outdoor units correct?

 

 

YES

 

 

 

Is the voltage across the outdoor terminal

NO

( 1 - 2 ) 220/230/240 VAC?

 

 

YES

 

 

 

 

 

NO

 

 

Are all the cords for compressor normal?

YES

Is the compressor motor winding normal? NO (Check the winding resistor.)

YES

NO

Is the capacitor for compressor normal?

 

 

YES

 

 

Is the overload relay normal?

NO

 

 

 

 

 

YES

 

 

 

 

 

Does the compressor start?

NO

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

Compressor starts but

 

 

it stops after a while?

 

 

 

YES

 

 

 

 

 

 

 

 

NO

 

Is the gas quantity normal?

 

(Check the pressure)

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor is defective

 

 

 

 

 

 

 

 

 

 

 

 

See "Power can not be turned on".

See "Power can not be turned on".

Relays (RY01, RY02)

or IC31 or IC30 is failure.

Correct cabling between indoor and outdoor units.

Cables between indoor and outdoor units are defective.

Re-wire or replace the defective cords.

Compressor is defective.

Capacitor is defective.

Overload relay is defective.

Compressor is defective.

Gas shortage (Gas leakage)

Replace the PC board.