Table 9-2-4

 

 

 

Block level

 

Diagnosis function

 

 

 

Check

 

Check

 

Air

 

 

Judgment and action

Block

Symptom

Conditioner

Condition

 

 

code

code

 

 

 

 

status

 

 

 

 

 

 

 

 

 

 

 

Indoor PC

 

Thermo sensor

Continued

Indicated when

1. Check thermo sensor.

 

board

 

short/break.

operation

detected abnormal

2.

If it is OK, check PC board.

 

 

 

Heat exchanger

Continued

Indicated when

1.

Check heat exchanger

 

 

 

sensor short/break.

operation

detected abnormal

 

sensor.

 

 

 

 

 

 

2.

If it is OK, check PC board.

 

 

 

Indoor fan lock,

All off

Indicated when

1.

Disconnect the power plug

 

 

 

abnormality of

 

detected abnormal

 

from AC outlet, and pull out

 

 

 

indoor fan.

 

 

 

the connector (CN10) for the

 

 

 

 

 

 

 

motor, then connect the plug

 

 

 

 

 

 

 

of AC power cord again and

 

 

 

 

 

 

 

turn the power on.

 

 

 

 

 

 

2. Check the voltage between

 

 

 

 

 

 

 

pin 1 and 2 of the connector

 

 

 

 

 

 

 

(CN10).

 

 

 

 

 

 

3.

If the output voltage is 35V,

 

 

 

 

 

 

 

PC board is OK, check

 

 

 

 

 

 

 

motor.

 

 

 

Abnormality of

All off

Indicated when

Replace PC board.

 

 

 

other indoor unit PC

 

detected abnormal

 

 

 

 

 

board.

 

 

 

 

 

Refrigerant

 

1) Gas shortage.

All off

Indicated when

1.

Check gas quantity.

 

system

 

(gas leak)

 

detected abnormal

 

(check gas leakage)

 

 

 

 

 

 

 

 

 

 

2) Other refrigerant

 

 

2.

If it is OK, check heat

 

 

 

cycle trouble.

 

 

 

 

 

 

 

 

exchanger sensor.

 

 

 

 

 

 

 

 

 

 

3) Heat exchanger

 

 

3.

If heat exchenger sensor is

 

 

 

sensor off/break/

 

 

 

 

 

 

 

 

OK. check overload relay and

 

 

 

short.

 

 

 

 

 

 

 

 

 

thermostat for compressor.

 

 

 

 

 

 

 

 

 

 

4) Overload relay

 

 

4.

If overload relay is OK, check

 

 

 

 

 

 

 

 

 

 

 

 

 

refrigerant cycle.

 

 

 

 

 

 

5.

If refrigerant cycle is OK,

 

 

 

 

 

 

 

check PC board.

Contents detected by the check codes “ ” to “ are stored in memory of the microcomputer even if the power supply is turned off. Therefore, contents of operations in the past are all displayed.