9-1-3. Misleading but Good Operations (Program Controlled Operation)

The microcomputer performs the operations listed in Table 9-1-1 to control the air conditioner. If a claim is made on the operation, check whether it corresponds to the contents in the Table 9-1-1. If it does, it is an indispensable operation for the control and mainte- nance of the air conditioner: it is not a failure of the unit.

 

 

Table 9-1-1

 

 

 

No.

Operation of air-conditioner

Description

 

 

 

1

When the power plug or the power cord

The OPERATION lamp flashes, indicating that power is turned

 

of the indoor unit is inserted, the

on. If this happens, push the START/STOP button once to cause

 

OPERATION lamp on the setting

the lamp to stop flashing. A power outage also causes the lamp

 

indication part flashes.

to flash.

 

 

 

2

Fan speed remains unchanged in the dry

Fan speed is automatically controlled in the dry mode.

 

mode.

 

 

 

 

3

Room temperature is in the range under

The compressor will not stop while the compressor on hold timer

 

which the compressor is turned off, but

(3-minutes timer) is actuated.

 

the compressor will not stop.

 

 

 

 

4

The compressor will not switch on or off

In the dry mode, the compressor goes on and off at regular

 

even when the thermo control is operated

intervals, independent of the thermo control.

 

in the dry operation.

 

 

 

 

5

Compressor does not work though room

Compressor does not work while the compressor restart delay

 

temperature is in the range of turning the

(3-min.) timer is active. The same is true after power is turned

 

compressor on.

on, as the time is still active.

 

 

 

6

During automatic operation, the

After selection of the cooling and dry operation, the operation

 

operation mode changes.

mode is selected again when the compressor off mode continues

 

 

for 15 min. according to the room temperature. And after selection

 

 

of the dry operation, the condition of the room temperature which

 

 

is Room temp. ³Set temp.+1 and which is Room temp.<Set

 

 

temp.–4 continues for 15 min., the operation mode is selected

 

 

again.

 

 

 

7

When the power is turned on, the

When the auto restart controlling is selected, the operation is

 

operation starts automatically.

performed automatically in the previous operation mode after

 

 

the power supply has been turned on.

 

 

 