6 F 3 H 1 0 0 1

Table 6.1 Control Functions

No.

Device

Name / Function

 

 

 

c

52R

Main circuit AC input circuit breaker

When the AC input is normal, power is

 

 

supplied to the UPS through this circuit

 

 

breaker.

d

72B

Main circuit DC input circuit breaker

When AC input has been cut off, power is

 

 

supplied from the battery to the UPS

 

 

through this circuit breaker.

 

52C

Bypass AC circuit breaker

e

When bypass power is supplied, power is

 

 

supplied to the load through this circuit

 

 

breaker.

f

52M

Maintenance bypass AC circuit breaker

When bypass power is supplied for UPS

 

 

maintenance, power is supplied to the

 

 

load through this circuit breaker.

g

52L

AC output circuit breaker

While UPS power or bypass power is

 

 

supplied, power is supplied to the load

 

 

through this circuit breaker.

h

8A

Control power source switch

When AC input is normal, pressing this

 

 

switch supplies power to the control power

 

 

source.

i

6CH

Precharge circuit button

Pressing this button supplies power to the

 

 

circuit that precharges the DC electrolytic

 

 

capacitor before power is supplied to

 

 

circuit breaker 52R.

 

 

 

Normal Status During Operation

ON

ON

ON

OFF

ON

ON

ON

Remarks

When the circuit breaker is tripped in manual mode, reset it by grasping the handle and pulling it down or to the right.

Certain systems are also provided with the switch 8D.

6.2 Circuit Configuration

UPS

52R

AC INPUT

 

BYPASS

52C

AC INPUT

 

72B

52L

AC OUTPUT

BATTERY

52M

Figure 6.2 Standard Circuit Configuration

- 13 -

Page 14
Image 14
Toshiba TOSNIC-7000S instruction manual Circuit Configuration