6 F 3 H 1 0 0 1
6.3Panel Controls
| When the unit has stopped due to failure, be sure to remove the | |
| memory card before resetting the LCD Failure Error screen on the | |
| panel, so you can give it to the service person. | |
| Resetting (restarting) the UPS without removing the memory card will | |
NOTES | delete the data needed to determine the cause of the failure. | |
Every effort has been made to ensure safety in unit handling. | ||
| ||
| However, when removing the memory card, do not touch the other | |
| sections of the unit. | |
| Touching the other sections of the unit may result in electric shock. | |
|
|
The locations of the controls on the panel are shown in Figure 6.3.1. For the functions of each of the controls, see Section 6.3.1 "Panel
i
(**)
~
UPS SUPPLY
~
WARNING
~
SCROLL
j
FAULT
UPS
c
e
d
AC INPUTCONVERTERINVERTER
| FLOATCHARGE |
| AC | ~ |
|
|
|
|
|
| |
BATTERIES | EQUALCHARGE |
| SWITCH | AC OUTPUT |
|
| DISCHARGE |
|
| ||
|
|
|
| ||
~ |
|
| BYPASS |
|
|
BYPASS INPUT |
|
| k | ||
| UPS | CHARGE | AC SWITCH | FAULT | |
| OPERATION |
|
|
|
|
| OPERATION STOP RUN | EQUAL | BYPASS UPS | RESET |
|
| FLOAT |
| |||
| INHIBITED |
|
|
| g |
|
|
|
|
| |
|
|
|
|
| f •(***) |
h(*)
Figure 6.3.1 Panel Controls
(For individual battery systems. For HS or AHH batteries.)
*This will be the "FLOAT" key for MSE individual battery systems.
**This will be the "PROTECTION" LED for MSE individual battery systems.
NOTE ***
Do not use the keypad on graphic display panel •.
This keypad is used to change the internal settings and should only be used by maintenance personnel.
It is not used during normal operation.
- 14 -