9.2.4 Scrolling Through LCD Screens in the Event of Failure

NOTES

When the unit has stopped due to failure, be sure to remove the memory card before resetting the LCD Failure Error screen on the panel, so you can give it to the service person.

Resetting (restarting) the UPS without removing the memory card will delete the data needed to determine the cause of the failure.

Every effort has been made to ensure safety in unit handling. However, when removing the memory card, do not touch the other sections of the unit.

Touching the other sections of the unit may result in electric shock.

This section describes how to scroll through the LCD screens when a failure has occurred (in other words, when Failure Data screens exist).

Figure 9.8 shows the locations of the scroll keys used to scroll through the LCD screens. See Table 9.9 and Figure 9.9 for a discussion of the scroll keys and how they are used for screen scrolling.

Note that pressing the "RESET" key k will delete the waveform data stored on the memory card as well as the Failure and Warning Data Screens. Be sure to remove the memory card before pressing the "RESET" key.

i

UPS SUPPLY

SCROLL

j

WARNING

FAULT

UPS

AC INPUT

CONVERTER

INVERTER

 

FLOATCHARGE

 

BATTERIES

EQUALCHARGE

 

 

DISCHARGE

 

BYPASS INPUT

UPS CHARGE

AC

SWITCH

AC OUTPUT

BYPASS

 

AC SWITCH

FAULT

k

OPERATION

OPERATION STOP

RUN

EQUAL

BYPASS

UPS RESET

FLOAT

INHIBITED

 

 

 

 

Figure 9.8 Position of Scroll Keys in Failure Data Screens

(For Individual battery systems. For HS or AHH batteries.)

- 48 -

Page 49
Image 49
Toshiba TOSNIC-7000S instruction manual Position of Scroll Keys in Failure Data Screens