8.3.4 Complete Shutdown

This section describes the procedure used to turn off the control power source and shut down the UPS completely (to turn everything up to the control power source off).

 

 

Table 8.4

Complete Shutdown

 

 

Step

Procedure

LCD/LED Status (After Execution)

 

 

1-4 Same as steps 1-4 in Section 8.3.3 "Stop."

 

 

 

5

When the message

 

BYPASS

 

 

 

 

appears, turn off the

 

 

 

 

 

main circuit AC input

 

 

 

 

 

 

circuit breaker (52R).

 

MOVE #52C AND #52L TO ‘ON’ POSITION

 

 

 

UPS

 

 

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

 

FLOAT CHARGE

 

AC

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

 

 

 

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

 

 

 

 

BYPASS

 

 

 

BYPASS INPUT

 

 

 

 

 

 

 

 

 

 

 

 

The "AC INPUT" LED unlit.

 

6

Turn off the AC output

 

 

 

 

 

 

circuit breaker (52L).

 

OPERATION GUIDANCE

 

 

 

 

 

MOVE #52C TO ‘OFF’ POSITION

 

 

 

UPS

 

 

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

 

FLOAT CHARGE

 

AC

 

 

 

 

 

 

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

BYPASS

 

 

 

BYPASS INPUT

 

 

 

 

 

 

 

 

 

 

 

 

The "AC INPUT" LED unlit.

 

7

Turn off the Bypass

 

OPERATION GUIDANCE

 

 

 

input circuit breaker

 

 

 

 

(52C).

 

MOVE #6CH TO ‘OFF’ POSITION

 

 

 

 

WAIT ABOUT 20 MINUTES

 

 

 

 

MOVE #8A TO ‘OFF’ POSITION

 

 

 

UPS

 

 

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

 

FLOAT CHARGE

 

AC

 

 

 

 

 

 

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

 

 

 

 

BYPASS

 

 

 

BYPASS INPUT

 

 

 

 

 

 

 

 

 

 

 

 

The "BYPASS INPUT" LED unlit.

 

- 35 -

Page 36
Image 36
Toshiba TOSNIC-7000S instruction manual 3 H 1 0 0 Complete Shutdown