8.3.6 Changing to Floating Charge etc. (for MSE individual battery)

Table 8.7 shows the procedure used to change manually from protective charge to floating charge.

This operation does not apply to shared battery systems.

(1)An MSE battery normally operate in floating charge mode.

(2)To prevent the battery temperature from rising, the mode changes automatically to protective charge mode when a "BATT FAULT1" (BATTERY OVER TEMP.) warning occurs.

(3)In protective charge mode, the battery is automatically charged at a voltage about 5% lower than normal (floating) charge when the battery temperature has risen above the rated value, in order to prevent deterioration caused by excessive charging at high temperatures.

(4)After a set amount of time has elapsed (about 6 hours), if the "BATT FAULT1" (BATTERY OVER TEMP.) warning message has disappeared, the mode will automatically change back to floating charge. As a result, it will not normally be necessary to change the mode manually as described below.

Table 8.7 Changing from Protective Charge to Floating Charge

Step

Procedure

LCD/LED Status (After Execution)

 

 

1

Check to make sure

 

 

 

 

 

 

that the

 

UPS SUPPLY

 

 

 

 

"PROTECTION" LED

 

AC-VO

200[V]

 

 

 

is lit..

 

 

 

 

 

AC- I O

50[%]

 

 

 

 

 

 

 

 

 

UPS

 

 

 

 

 

 

2

Check to make sure

AC INPUT

CONVERTER

INVERTER

 

 

 

 

 

 

 

 

that the "BATT FAULT1"

 

FLOAT CHARGE

 

AC

 

 

 

 

 

 

 

warning message has

BATTERIES

PROTECTION

 

SWITCH

AC OUTPUT

 

 

 

 

 

 

 

disappeared.

 

DISCHARGE

 

 

 

 

 

 

 

 

 

 

 

 

 

BYPASS

 

 

 

BYPASS INPUT

 

 

 

 

 

 

 

 

 

3

Hold down the

 

 

 

 

 

 

"FLOAT" key (h in

 

UPS SUPPLY

 

 

 

 

Figure 6.3.1 on page

 

AC-VO

200[V]

 

 

 

14) for at least 0.5

 

 

 

 

 

AC- I O

50[%]

 

 

 

second.

 

 

 

 

 

 

 

 

 

 

Change to floating

 

 

 

 

 

 

charge is complete.

UPS

 

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

 

FLOAT CHARGE

 

AC

 

 

 

 

 

 

 

 

BATTERIES

PROTECTION

 

SWITCH

 

 

 

 

 

 

 

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

 

 

 

 

BYPASS

 

 

 

BYPASS INPUT

 

 

 

 

 

 

 

 

 

 

 

 

The "FLOAT CHARGE" LED lit.

 

 

 

 

The "PROTECTION" LED unlit.

 

- 39 -

Page 40
Image 40
Toshiba TOSNIC-7000S instruction manual Changing from Protective Charge to Floating Charge