Table 8.9 Changing From Maintenance Bypass to UPS Power Supply

Step

Procedure

LCD/LED Status (After Execution)

 

 

1

Same as steps 1-4 in

 

BYPASS

 

 

 

 

Section 8.3.1 “Startup”

 

 

 

 

 

 

 

MOVE #52R TO ‘ON’ POSITION

 

 

 

UPS

 

 

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

 

FLOAT CHARGE

 

AC

 

 

 

 

 

 

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

 

BYPASS

 

 

BYPASS INPUT

 

 

 

 

 

 

 

52R

72B

52C

52M

52L

MCCB

OFF OFF ON OFF ON

2Turn OFF maintenance

bypass AC circuit breaker

BYPASS

52M. *,**,***

 

MOVE #52R TO ‘ON’ POSITION

UPS

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

FLOAT CHARGE

 

AC

 

 

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

 

 

DISCHARGE

 

 

AC OUTPUT

BYPASS

BYPASS INPUT

52R

72B

52C

52M

52L

MCCB

OFF OFF ON ON ON

3Same as steps 5-11 in Section 8.3.1 “Startup”

Change to UPS power supply complete.

*During load operation, ALWAYS operate the circuit breakers in the following order: 52C ON 52L ON 52M OFF

**UPS power supply is disabled when the 52M circuit breaker is in the on state.

***This operation is different from that displayed in the help message on the screen. Be sure to perform the operation as described here.