6 F 3 H 1 0 0 1
Table 8.9 Changing From Maintenance Bypass to UPS Power Supply
Step | Procedure | LCD/LED Status (After Execution) |
|
| ||
1 | Same as steps |
| BYPASS |
|
|
|
| Section 8.3.1 “Startup” |
|
|
|
| |
|
|
| MOVE #52R TO ‘ON’ POSITION |
| ||
|
| ~ | ~ | ~ | UPS |
|
|
|
|
|
| ||
|
| AC INPUT | CONVERTER | INVERTER |
|
|
|
|
| FLOAT CHARGE |
| AC | ~ |
|
|
|
|
|
| |
|
| BATTERIES | EQUAL CHARGE |
| SWITCH |
|
|
|
| DISCHARGE |
|
| AC OUTPUT |
|
|
|
|
|
|
~ |
| BYPASS |
|
|
BYPASS INPUT |
|
|
| |
|
|
|
| |
52R | 72B | 52C | 52M | 52L |
MCCB | OFF OFF ON OFF ON |
2Turn OFF maintenance
bypass AC circuit breaker | BYPASS |
52M. *,**,*** |
|
MOVE #52R TO ‘ON’ POSITION
~ | ~ | ~ | UPS |
|
|
|
| ||
AC INPUT | CONVERTER | INVERTER |
|
|
| FLOAT CHARGE |
| AC | ~ |
|
|
|
| |
BATTERIES | EQUAL CHARGE |
| SWITCH |
|
|
|
|
| |
| DISCHARGE |
|
| AC OUTPUT |
~
BYPASS
BYPASS INPUT
52R | 72B | 52C | 52M | 52L |
MCCB | OFF OFF ON ON ON |
3Same as steps
→Change to UPS power supply complete.
*During load operation, ALWAYS operate the circuit breakers in the following order: 52C ON → 52L ON → 52M OFF
**UPS power supply is disabled when the 52M circuit breaker is in the on state.
***This operation is different from that displayed in the help message on the screen. Be sure to perform the operation as described here.
-41 -