6 F 3 H 1 0 0 1

Table 7.1 Display Panel Functions (For HS or AHH individual battery systems)

No.

Name

Function

11

LCD INDICATOR

Displays help messages, measurement data and

 

 

warning descriptions. For more information, see Section

 

 

7.2 "LCD Display."

12

UPS SUPPLY LED

This LED lights up when the UPS is operating.

 

 

 

13

WARNING LED

This LED blinks in the event of an warning.

 

 

 

14

FAULT LED

This LED lights up in the event of a UPS failure.

 

 

 

15

AC INPUT LED

This LED lights up when the AC input circuit breaker

 

 

(52R) has gone ON.

 

 

 

16

CONVERTER LED

This LED is unlit when the converter has stopped

 

 

operating. It blinks when the converter is starting up

 

 

and is lit when startup is complete.

 

 

 

17

INVERTER LED

This LED is unlit when the inverter has stopped

 

 

operating. It blinks while the inverter is starting up and is

 

 

lit when startup is complete.

 

 

 

18

AC OUTPUT LED

This LED lights up when the AC output circuit breaker

 

 

(52L) is ON and AC voltage has been established.

 

 

 

19

BATTERIES LED

This LED lights up when the main circuit DC input circuit

 

 

breaker (72B) has goes ON.

 

 

 

20

FLOATING CHARGE

This LED lights up when the charging mode is set to

 

LED**

floating charge.

21EQUAL CHARGE LED*, ** This LED lights up when the charging mode is set to equalized charge.

22

DISCHARGE LED

This LED lights up when the battery is being discharged.

23

BYPASS INPUT LED

This LED lights up when the bypass input circuit breaker

 

 

(52C) has gone ON.

 

 

 

24

UPS LED

This LED lights up when the selector switch is set to the

 

 

UPS side.

 

 

 

25

BYPASS LED

This LED lights up when the selector switch is set to the

 

 

bypass side.

*This becomes the PROTECTION LED in MSE individual battery systems.

**This switch is not present in shared battery systems.