6 F 3 H 1 0 0 1

Table 8.1 Startup Procedures (continued)

Step

Procedure

LCD/LED Status (After Execution)

 

 

7

Hold down the "RUN"

 

 

 

 

 

 

key (d in Figure 6.3.1

 

BYPASS

 

 

 

 

on page 14) for at least

 

 

 

 

 

 

0.5 second.

 

UPS START-UP

 

 

 

 

 

 

 

 

 

UPS

 

 

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

 

FLOAT CHARGE

 

AC

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

 

 

 

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

 

 

 

 

BYPASS

 

 

 

BYPASS INPUT

 

 

 

 

 

 

 

 

 

 

 

The "CONVERTER" and "INVERTER" LEDs blinking.

8

Wait several seconds

 

 

 

 

 

 

for the startup process

 

BYPASS

 

 

 

 

to finish.

 

 

 

 

 

 

 

 

MOVE #72B TO ‘ON’ POSITION

 

 

 

UPS

 

 

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

 

FLOAT CHARGE

 

AC

 

 

 

 

 

 

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

BYPASS

 

 

 

BYPASS INPUT

 

 

 

 

 

 

 

 

 

 

 

The "CONVERTER" and "INVERTER" LEDs lit.

9

When the message

 

 

 

 

 

 

appears, turn on the

 

BYPASS

 

 

 

 

main circuit DC input

 

AC-VO

200[V]

 

 

 

circuit breaker (72B).

 

 

 

 

 

AC- I O

50[%]

 

 

 

 

 

 

 

 

 

 

PRESS ‘UPS’ SWITCH

 

 

 

UPS

 

 

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

 

FLOAT CHARGE

 

AC

 

 

 

 

 

 

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

 

 

 

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

BYPASS

 

 

 

BYPASS INPUT

 

 

 

 

 

 

 

 

 

 

 

The "BATTERIES" and "FLOAT CHARGE" LEDs lit.

- 29 -