8.3.7 Changing the Power Supply to Maintenance Bypass

This UPS must be completely shut down when performing maintenance and inspections. In such cases, the power supply to the load will go through the maintenance bypass. Table 8.8 shows the procedure used to change the power supply to this maintenance bypass. Table 8.9 shows how to change the power supply from the maintenance bypass back to the UPS.

Table 8.8 Changing From UPS to maintenance Bypass Power Supply

Step

Procedure

LCD/LED Status (After Execution)

 

 

1-3 Same as steps 1-5 in Section 8.3.4 "Stop."

 

 

 

4

Turn ON maintenance

 

BYPASS

 

 

 

 

bypass AC circuit

 

 

 

 

 

breaker 52M. *,**

 

 

 

 

 

 

 

 

MOVE #52C AND #52L TO ‘ON’

 

 

 

UPS

 

 

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

 

FLOAT CHARGE

 

AC

 

 

 

 

 

 

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

 

 

 

 

BYPASS

 

 

 

BYPASS INPUT

 

 

 

 

 

 

 

 

 

 

52R

72B

52C

52M

52L

MCCB

OFF

OFF

ON

ON

ON

5

Perform steps 6

When the UPS is shutdown completely, nothing at all will be

 

through 11 in Table 8.4 displayed on the LCD screen and all LEDs will be unlit.

 

“Complete Shutdown”

 

 

 

 

 

 

 

on page 34 to shut

 

52R

72B

52C

52M

52L

 

down the UPS

 

 

completely.

MCCB

OFF

OFF

OFF

ON

OFF

 

Change to

 

 

 

 

 

 

 

 

maintenance bypass

 

 

 

 

 

 

 

power supply

 

 

 

 

 

 

 

complete.

 

 

 

 

 

 

*During load operation, always operate the circuit breakers in the following order : 52M ON52lL OFF52C OFF

**When power is supplied to the UPS, circuit breaker 52M cannot be turned on.

- 40 -

Page 41
Image 41
Toshiba TOSNIC-7000S instruction manual 3 H 1 0 0 Changing the Power Supply to Maintenance Bypass