6 F 3 H 1 0 0 1

6. Controls and Circuit Configuration

If the unit begins to emit smoke or strange odors, immediately WARNIN turn off circuit breakers 52R and 72B.

G Continued use may result in fire. Contact the Toshiba Service

Center .

6.1 Panel Controls

Figure 6.1 and Table 6.1 show the locations and functions of the controls used for the circuit configurations (see Figures 6.2) on the UPS.

Do not turn the circuit breakers ON when control power source switch (8A) is OFF.

This may result in failure.

Do not turn the control power source switch (8A) to the OFF position when the circuit breakers are ON.

NOTES

This may result in failure.

*Certain systems are also provided with a control power source switch (8D).

This switch has the same functions as the switch 8A.

If an MCCB with auxiliary handles is used as the circuit breaker, use the auxiliary handles during operation.

Example: 300 kVA

c52R

d72B

 

e52R

 

 

f52M

 

 

g52L

 

h8A

 

 

 

 

i6CH

The figure above is only an example; the layout may be different depending on capacity and system configuration.

Figure 6.1 Location of Control (in panel)

- 12 -

Page 13
Image 13
Toshiba TOSNIC-7000S Controls and Circuit Configuration, Panel Controls, Example 300 kVA C52R D72B E52R F52M G52L H8A I6CH