8.3.3 Stop

Table 8.3 shows the procedure used to stop the UPS.

Table 8.3 Stop

Step

Procedure

LCD/LED Status (After Execution)

 

 

1

Change to bypass

 

 

 

 

 

 

supply as described in

 

BYPASS

 

 

 

 

Table 8.2 on page 31.

 

AC-VO

200[V]

 

 

 

 

 

 

 

 

 

 

AC- I O

50[%]

 

 

 

 

 

PRESS ‘UPS’ SWITCH

 

 

 

UPS

 

 

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

 

FLOAT CHARGE

 

AC

 

 

 

 

 

 

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

 

AC OUTPUT

 

 

 

DISCHARGE

 

 

 

 

 

 

 

 

 

 

 

 

BYPASS

 

 

 

BYPASS INPUT

 

 

 

 

 

 

 

 

 

 

The “UPS” LED unlit and “BYPASS” LED lit.

2

Hold down the "STOP"

 

 

 

 

 

 

key (e in Figure 6.3.1

 

BYPASS

 

 

 

 

on page 14) for at least

 

RESTART : PRESS ‘RUN’ SWITCH

 

 

0.5 second.

 

 

 

 

SHUTDOWN : MOVE #72B TO ‘OFF’

 

 

 

 

 

 

 

UPS

 

 

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

 

FLOAT CHARGE

 

AC

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

 

 

 

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

 

 

 

 

BYPASS

 

 

 

BYPASS INPUT

 

 

 

 

 

 

 

 

 

 

 

 

The “FLOAT CHARGE” and “CONVERTER”

 

 

 

and “INVERTER” LEDs unlit.

 