6 F 3 H 1 0 0 1

Table 9.7 Warning-3 (Operation control)

#

Item

LCD Message

Description

 

 

Indication

 

1

59C

BYPASS OV

Bypass input voltage is high.

2

27C

BYPASS UV

Bypass input voltage is low.

3

95C

BYPASS ASY

Bypass input frequency error.

Table 9.8 Warning - 4 and 5 (Guidance)

#

Item

LCD Message

Description

 

 

Indication

 

1

49H

LOAD LIMIT

Load has exceeded prescribed level.

2

51LI

O/P OC (PEAK)

Load current peak value is high.

3

72BO

72B MIS OPE.

72B has gone off during operation.

 

 

 

(Including operation error)

4

26B

BATT FAULT1

Battery temperature has risen.

5

33B

BATT FAULT2 *

Battery fluid level has gone below prescribed level.

6

80B2

BATT UV (ALM)

Battery voltage is near discharged voltage.

7

76CH

BATT OC

Charging current is high.

8

47R

AC PHASE ERR

Phase ration of AC input is reserved.

9

47C

BYPASS ERR

Phase ration of bypass input is reserved.

10

48S

STARTUP ERR

Startup was not completed.

11

52CO

52C MIS OPE.

52C has gone off during opearion.

 

 

 

(Including operation error)

12

83F

SWITCH ERR

Changeover switch error.

* This message is deleted in case of a sealed type NS and HHS or MSE battery.

- 47 -

Page 48
Image 48
Toshiba TOSNIC-7000S 59C, Bypass input voltage is high, 27C, Bypass input voltage is low, 95C, 49H, 51LI, 72BO, 26B, 33B