6 F 3 H 1 0 0 1

8.3Procedures

8.3.1 Startup

Table 8.1 shows the procedure used to start up the UPS.

LED status

: Unlit

: Lit

: Blinking

 

 

 

 

 

 

Table 8.1

Startup Procedures

 

 

Step

Procedure

 

LCD/LED Status (After Execution)

 

 

1

Turn on the control

 

OPERATION GUIDANCE

 

 

 

power supply switch

 

 

 

 

 

 

 

 

 

 

(8A) on the panel.

 

MOVE #52C AND #52L TO ‘ON’ POSITION

 

 

 

 

 

 

 

 

 

UPS

 

 

 

 

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

 

 

FLOAT CHARGE

 

AC

 

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

BYPASS

 

 

 

 

BYPASS INPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The "BYPASS" LED lit.

 

2

Turn on the bypass AC

 

BYPASS

 

 

 

 

input 52C and the AC

 

 

 

 

 

 

 

 

 

 

 

output 52L circuit

 

MOVE #6CH TO ‘ON’ POSITION

 

 

breakers.

 

 

 

 

(The UPS will change

 

 

 

 

 

 

to bypass power

UPS

 

 

supply status and AC

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

output voltage will be

 

 

 

 

 

 

AC

 

generated.)

 

 

FLOAT CHARGE

 

 

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

BYPASS

 

 

 

 

BYPASS INPUT

 

 

 

 

 

 

 

 

 

 

 

The "BYPASS INPUT" and The "OUTPUT"LEDs lit.

3

Turn on the precharge

BYPASS

 

 

 

 

circuit switch (6CH)*.

 

 

 

 

 

 

 

 

 

 

 

WAIT FOR A WHILE

 

 

UPS

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

FLOAT CHARGE

 

AC

 

 

 

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

 

 

 

 

 

AC OUTPUT

 

 

DISCHARGE

 

 

 

 

 

 

 

 

 

 

BYPASS

 

 

 

 

 

 

BYPASS INPUT

*The control power supply switch 8A is left in the on state (Do not turn this switch off.)

-27 -