6 F 3 H 1 0 0 1

8.3.5Changing Between Floating Charge and Equalized Charge (For HS or AHH individual battery systems)

This section describes the procedure used to change the charging mode. This operation does not apply to shared battery systems.

(1)Table 8.5 shows the procedure used to change manually from floating charge to equalized charge.

Table 8.5 Changing From Floating Charge to Equalized Charge

Step

Procedure

LCD/LED Status (After Execution)

 

1

Check to make sure

 

 

 

 

 

 

that the "FLOAT

 

UPS SUPPLY

 

 

 

 

CHARGE" LED is lit.

 

AC-VO

 

200[V]

 

 

 

 

 

 

 

 

 

AC- I O

 

50[%]

 

 

 

UPS

 

 

 

 

 

 

 

 

AC INPUT

CONVERTER

INVERTER

 

 

 

 

 

 

 

 

 

FLOAT CHARGE

 

AC

 

 

 

 

 

 

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

 

 

 

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

 

 

 

 

BYPASS

 

 

 

BYPASS INPUT

 

 

 

 

 

 

 

 

 

2

Hold down the "FLOAT

 

 

 

 

 

 

/ EQUAL" key (h in

 

UPS SUPPLY

 

 

 

 

Figure 6.3.1 on page

 

AC-VO

 

200[V]

 

 

14) for at least 0.5

 

 

 

 

 

AC- I O

 

50[%]

 

 

second.

 

 

 

 

 

 

 

 

 

 

Change to

 

 

 

 

 

 

equalized charge is

UPS

 

 

 

 

 

 

complete.

AC INPUT

CONVERTER

INVERTER

 

 

 

 

 

 

 

FLOAT CHARGE

 

AC

 

 

 

 

 

 

 

 

BATTERIES

EQUAL CHARGE

 

SWITCH

 

 

 

 

DISCHARGE

 

 

AC OUTPUT

 

 

 

 

 

 

 

 

 

 

BYPASS

 

 

 

BYPASS INPUT

 

 

 

 

 

 

 

 

 

The "EQUAL CHARGE" LED lit.

The "FLOAT CHARGE" LED unlit.

*In equalized charge mode, the battery is charged for a set period of time at a voltage about 5% (depending on the type of battery) higher than normal (floating) charge, in order to prevent variations in battery performance. This must be done about once every six months, in spring and autumn if possible.

The TOSNIC-7000S UPS is equipped with a function that performs the equalized charging process automatically when restoring the battery charge after a power outage or the like.

-37 -

Page 38
Image 38
Toshiba TOSNIC-7000S instruction manual Changing From Floating Charge to Equalized Charge