Examples: For the following, the Q1234 VAh has a current value of 123,456,789.0123 VAh.

Register CA00H

Digits

Unit

D.P.

Pattern

Reading

Display

Hex

Binary

Hex

Decimal

 

 

 

 

 

20xxH

001 00 000

3 Digits

VAh, 100

0

xxx VAh

00000315H

789

789 VAh

8BxxH

100 01 011

6 Digits

kVAh, 103

3

xxx.xxx kVAh

0006F855H

456789

456.789 kVAh

88xxH

100 01 000

6 Digits

kVAh, 103

0

xxxxxx kVAh

0001E240H

123456

123,456 kVAh

93xxH

100 10 011

6 Digits

MVAh, 106

3

xxx.xxx MVAh

0001E240H

123456

123.456 MVAh

72xxH

011 10 010

5 Digits

MVAh, 106

2

xxx.xx MVAh

00003039H

12345

123.45 MVAh

C2xxH

110 00 010

8 Digits

VAh, 100

2

xxxxxx.xx VAh

02B90135H

45678901

456,789.01 VAh

7.51: Update Settings Block (52975-53248)

User Memo Field (256 bytes)- 128 registers, 256 bytes. User can write any notes up to 255 charac- ters in this memo field.

Name of User Who Last Updated the Profile (256 bytes) - These registers are used internally with the software. No interactions are required by the user.

Device Profile Version (Year, Month/Day, Build) - These registers have the updated date for Device Profile. These registers are used internally with the software. No interactions are required by the user.

Program Software ID - These registers have software ID. These registers are used internally with the software. No interactions are required by the user.

GE Device Type (Base Unit, Option 1/Option 2, Option 3/Option 4) - These registers have information on what type of GE meters that the software is communicating to.

These registers are used internally with the software. No interactions are required by the user.

Update Programming Software Version Number (Major, Minor, Revision) - These registers have software version number. These registers are used internally with the software. No interactions are required by the user.

7-33

Page 353
Image 353
GE EPM 9650/9800 manual Update Settings Block