A bit value of 1 means the physical relay needs to be updated, a bit value of 0 means the physical relay does not need to be updated.

Example:

Register 06009, Relays Pending Updates 1-16, might contain the following data:

Address

 

 

 

 

 

 

 

06009

 

 

 

 

 

 

 

Value

 

 

 

 

 

 

 

0461H

 

 

 

 

 

 

 

Bytes

 

 

 

04H

 

 

 

 

 

 

61H

 

 

 

Bits

0

0

0

0

0

1

0

0

0

1

1

0

0

0

0

1

Point

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Relay

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

Update?

 

 

 

 

 

Yes

 

 

 

Yes

Yes

 

 

 

 

Yes

Interpretation Relays 6, 10, 11 and 16 need to be updated, all others are in their correct states.

3.38: Type F38 Shadowed Relay States

Length: 1 Register (2 bytes)

This register has two bytes. Each byte has eight bits. The bits in these bytes are associated with the 16 Relays, the most significant byte with Relay 1 through to the least significant bit of the least significant byte with Relay 16.

A bit value of 1 means the relay is supposed to be energized (connected to Normal Open), a bit value of 0 means the relay is supposed to be de-energized (connected to Normal Close). These states have not necessarily been confirmed by polling the relay device.

Example:

Register 06010, Shadowed Relay States 1-16, might contain the following data:

Address

 

 

 

 

 

 

 

06010

 

 

 

 

 

 

 

Value

 

 

 

 

 

 

 

0440H

 

 

 

 

 

 

 

Bytes

 

 

 

04H

 

 

 

 

 

 

40H

 

 

 

Bits

0

0

0

0

0

1

0

0

0

1

0

0

0

0

0

0

Point

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Relay

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

State (NO/NC)

NC

NC

NC

NC

NC

NO

NC

NC

NC

NO

NC

NC

NC

NC

NC

NC

Interpretation Relays 6 and 10 are supposed to be energized, all other de-energized, not necessarily confirmed.

3-27

Page 245