7.42: Internal Modem Card Settings Block (50177-50268)

Ring number - 1 byte. The EPM device will answer after this number of rings (1 to 9).

Baud Rate - 1 byte. This will program the baud rate of the gateway.

 

EPM Internal Modem Card Baud Rate Settings

Index

Baud Rate (INP 1)

Baud Rate (INP 2)

0

57600

115200

1

57600

57600

2

38400

38400

3

19200

19200

4

9400

9600

5

4800

4800

6

57600

2400

7

57600

1200

8

57600

9600

9

57600

9600

10-255

57600

9600

Port Configuration - 1 byte. Pass Through Port Configuration.

Bit 2 - Bit 0

Parity

000None

001Even

010Odd

011Mark

100Space

101Space

110Space

111Space

Bit 3:

A value of 0 means 8-data bits.

A value of 1 means 7-data bits.

Call Delay Timer Limit - 1 register, 2 bytes. User-set variable that defines the number of seconds the modem will wait before processing a callback event (0-240 seconds). Applies to calls caused by Limit or Input Status conditions.

Activity Timeout Limit - 1 byte. User-set value that is the number of minutes of inactivity (no communication activity) that is allowed on an open modem connection before the modem will terminate the connection (1-30 minutes)