7.15: Device Label Settings Block (45969-45992).

Meter Designation - 8 registers, 16 bytes ASCII.

Auxiliary Voltage Label - 8 registers, 16 bytes ASCII.

Measured Neutral Current Label - 8 registers, 16 bytes ASCII.

7.16: Network Settings Block (45993-46016).

IP Address - 2 registers, 4 bytes. Each byte has unsigned integer value.

Subnet Mask - 2 registers, 4 bytes. Each byte has unsigned integer value.

Default Gateway - 2 registers, 4 bytes. Each byte has unsigned integer value.

Port 2 Baud Rate - 1 byte, unsigned integer.

Port 2 Baud Rate Values

Value

Baud Rate

0

4800

1

9600

2

19200

3

38400

4

57600

5

115200

Gateway Delay - 1 byte, unsigned integers.

Gateway Delay in Milliseconds

Value

Delays in milliseconds (ms)

0

0

1

15

2-255

30-3825

Mode 1 - Network Mode 1. 1 register, only High Byte is used.

Bit 7: IP Address Resolution

A bit value of 1 means use DHCP server.

A bit value of 0 means use static IP address programmed into the meter. Bits 0-6: Reserved

Computer Name - 8 registers, 16 bytes ASCII.

Server IP Address - 2 registers, 4 bytes. Each byte has unsigned integer values.

7-9