7-9
7.15: Device Label Settings Block (45969-45992).
Meter Designation - 8 registers, 16 bytes ASCII.
Auxiliary Voltage Label - 8 registers, 16 bytes ASCII.
Measured Neutral Current Label - 8 registers, 16 bytes ASCII.
7.16: Network Settings Block (45993-46016).
IPAddress - 2 registers, 4 bytes. Each byte has unsigned integer value.
Subnet Mask - 2 registers, 4 bytes. Each byte has unsigned integer value.
Default Gateway - 2 registers, 4 bytes. Each byte has unsigned integer value.
Port 2 Baud Rate - 1 byte, unsigned integer.
Gateway Delay - 1 byte, unsigned integers.
Mode 1 - Network Mode 1. 1 register, only High Byte is used.
Bit 7: IPAddress Resolution
Abit value of 1 means use DHCP server.
Abit value of 0 means use static IP address programmed into the meter.
Bits 0-6: Reserved
Computer Name - 8 registers, 16 bytes ASCII.
Server IPAddress - 2 registers, 4 bytes. Each byte has unsigned integer values.
Value Baud Rate
0 4800
1 9600
2 19200
3 38400
4 57600
5 115200
Port 2 Baud Rate Values
Delays in milliseconds (ms)Value
00
115
2-255 30-3825
Gateway Delay in Milliseconds