7.8: External Analog Input Module Settings Block (45809-45812).

Up to 4 External Analog Input Modules can be addressed in this block.

Address - 2 bytes, unsigned integers.

A value of 0x0FFFF for an address indicates that this device is unused.

7.9: External Analog Output Module Settings Block (45813-45892).

Up to 4 External Analog Output Modules can be addressed in this block.

Address - 2 bytes, unsigned integers.

A value of 0x0FFFF for an address indicates that this device is unused.

Line Number - 2 bytes, unsigned integers.

Point Number - 1 byte, unsigned integers.

Line Number and Point Number will point which limit is going to be used for each output of the External Analog Output Module.

7.10: External KYZ Output Module Settings Block (45893-45907).

Up to 4 External KYZ Output Modules can be addressed in this block.

Address - 2 bytes, unsigned integers.

A value of 0x0FFFF for an address indicates that this device is unused.

The energy assignments are as follows:

 

KYZ Output Relay Byte Energy Assignments

Value

Energy Assignment

0

Disabled

1

Q (1+4) WH

2

Q1 VAH

3

Q1 VARH

4

Q4 VAH

5

Q4 VARH

6

Q (2+3) WH

7

Q2 VAH

8

Q2 VARH

9

Q3 VAH

10

Q3 VARH

11-18

Internal Inputs Accumulations 1-8

19-22

Internal Input Aggregator 1-4

23-30

External Digital Input Module 1 in Accumulator 1-8

31-38

External Digital Input Module 2 in Accumulator 1-8

39-46

External Digital Input Module 3 in Accumulator 1-8

47-54

External Digital Input Module 4 in Accumulator 1-8

7-6

Page 326