5.5: Calibration Interface

Manual Adjustment Interface

Modbus Register

Dual Port

 

Address

Name

Address

Decimal

Hex

 

 

 

57349

0x0E004

0x00083

Select Voltage 120V Gain (240V if 300V Option)

57350

0x0E005

0x00084

Select Current 150mA Gain (30mA if Class 2 Option)

57351

0x0E006

0x00085

Select Current 250mA Gain (50mA if Class 2 Option)

57352

0x0E007

0x00086

Select Current 500mA Gain (100mA if Class 2 Option)

57353

0x0E008

0x00087

Select Current 1A Gain (200mA if Class 2 Option)

57354

0x0E009

0x00088

Select Current 2.5A Gain (200mA if Class 2 Option)

57355

0x0E00A

0x00089

Select Current 5A Gain (1A if Class 2 Option)

57356

0x0E00B

0x0008A

Autocalibrate the above gain point on all phases

57357

0x0E00C

0x0008B

Increment selected calibration value for A Phase

57358

0x0E00D

0x0008C

Decrement selected calibration value for A Phase

57359

0x0E00E

0x0008D

Increment selected caliabration value for B Phase

57360

0x0E00F

0x0008E

Decrement selected calibration value for B Phase

57361

0x0E010

0x0008F

Increment selected calibration value for C Phase

57362

0x0E011

0x00090

Decrement selected calibration value for C Phase

57363

0x0E012

0x00091

Increment selected calibration value for X Phase

57364

0x0E013

0x00092

Decrement selected calibration value for X Phase

57365

0x0E014

0x00093

Enter Calibration Mode

57366

0x0E015

0x00094

Manual Calibration of Gains

57367

0x0E016

0x00095

First Time CTPT Compensation selection

57368

0x0E017

0x00096

Manual Calibration of Phase Compensation

57369

0x0E018

0x00097

Increment/Decrement by 1 count

57370

0x0E019

0x00098

Increment/Decrement by 10 counts

57371

0x0E01A

0x00099

Manual Reference Calibration

57372

0x0E01B

0x0009A

Calibration Status Reset

57373

0x0E01C

0x0009B

Select Current 500mA Phase Compensation (100mA if Class 2)

57374

0x0E01D

0x0009C

Select Current 1A Phase Compensation (200mA if Class 2)

57375

0x0E01E

0x0009D

Select Current 5A Phase Compensation (1A if Class 2)

57376

0x0E01F

0x0009E

Select Current 10A Phase Compensation (2A if Class 2)

57377

0x0E020

0x0009F

Select Current 2.5A Phase Compensation (500mA if Class 2)

57378

0x0E021

0x000A0

Preload CTPT Compensation with Initial Calibration Values

5-15