3.45: Type F45 Analog Input Modules Data Status

Length: 2 Registers (4 bytes)

This register has two bytes. Each byte has eight bits. The bits in these bytes are associated with the status of the data received from the Analog Input Modules as follows:

Reg

Bit

Point

Meaning

0

15 (MSB)

0

Status of Analog Input 1, Module 1 (Modbus Register 173AH)

0

14-8

1-7

Status of Analog Input 2-8, Module 1 (Modbus Register 173BH-174IH)

0

7-0

8-15

Status of Analog Input 1-8, Module 2 (Modbus Register 1742H-1749H)

1

15-8

16-23

Status of Analog Input 1-8, Module 3 (Modbus Register 174AH-175IH)

1

7-0

24-31

Status of Analog Input 1-8, Module 4 (Modbus Register 1752H-1759H)

Analog Input Module Data Status:

A bit value of 0 means that the data from this Analog Input Module is not yet valid. Either the module is not present or has not yet been polled.

A bit value of 1 means that the data from this Analog Input Module has been polled at least once and is valid.

Example:

Register 06112, Analog Input Modules Data Status, might contain the following data:

Addr

 

 

 

 

 

 

 

 

06112

 

 

 

 

 

 

 

Value

 

 

 

 

 

 

 

 

8000H

 

 

 

 

 

 

 

Bytes

 

 

 

 

80H

 

 

 

 

 

 

 

00H

 

 

 

Bits

1

1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Point

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Analog Input

1

1

1

1

1

1

1

1

2

2

2

2

2

2

2

2

Module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

Status

OK

OK

-

-

-

-

-

-

-

-

-

-

-

-

-

-

 

 

Inputs 1-2 of Analog Input Module 1 are valid (Registers 173AH-173BH),

 

Interpretation

 

 

 

 

Inputs 3-8 of Analog Input Module 1 are not valid,

 

 

 

 

 

 

 

Inputs 1-8 of Analog Input Module 2-4 are not valid.

 

 

 

3-33

Page 251
Image 251
GE EPM 9650/9800 manual Type F45 Analog Input Modules Data Status, Reg Bit Point, Bits Point Analog Input Module Status