6-35
6 binary 0-59 second
7 binary 0-100 centisecond
The source or meaning of the timestamp depends on the type of record being recorded.
If this record was recorded while the meter was in Test Mode, then the most significant bit of the
centisecond byte will be set.
The next byte is a code to indicate the type of record:
0x000 Power
0x001 Password
0x002 Change Programmable Settings
0x003 Change Firmware
0x004 Change Time
0x005 Test Mode
0x006 Log Download
0x007 Feature Reset
0x008-0x0FF Undefined
The meaning of the remaining 7 bytes (from now on referred to as sub-fields) depends on the type of
record.
QPower Record
The first byte of the sub-fields indicates whether power was lost or regained at the recorded time:
0x000 Power was lost
0x001 Normal operation was restored
0x002-0x0FF Undefined
The remaining 6 bytes of the sub-fields are undefined.
QPassword Record
The first byte of the sub-fields indicates what action occurred at the recorded time:
0x000 Password Protection was Enabled.
0x001 Password Protection was Disabled.
0x002 The Level 1 Password was changed.
0x003 The Level 2 Password was changed.
0x004 Level 1 access was granted.
0x005 Level 2 access was granted.
0x006 An invalid password was supplied.
0x007-0x0FF Undefined