Address

Line

Pt

DNP

Description

Range

Units

Type

R/W

 

 

 

Obj

 

 

 

 

 

 

00469

116

2

30

Minimum Thermal Average Phase C Power Factor Quadrant 1

0.999

/ 0

0.001 PF

F8

R

00470

117

0

30

Minimum Thermal Average Power Factor Quadrant 1

0.999

/ 0

0.001 PF

F8

R

00471

118

0

30

Minimum Thermal Average Phase A Power Factor Quadrant 2

1.999

/ /1.000

0.001 PF

F8

R

00472

118

1

30

Minimum Thermal Average Phase B Power Factor Quadrant 2

1.999

/ /1.000

0.001 PF

F8

R

00473

118

2

30

Minimum Thermal Average Phase C Power Factor Quadrant 2

1.999

/ /1.000

0.001 PF

F8

R

00474

119

0

30

Minimum Thermal Average Power Factor Quadrant 2

1.999

/ /1.000

0.001 PF

F8

R

00475

120

0

30

Minimum Thermal Average Phase A Power Factor Quadrant 3

2.999

/ 2.000

0.001 PF

F8

R

00476

120

1

30

Minimum Thermal Average Phase B Power Factor Quadrant 3

2.999

/ 2.000

0.001 PF

F8

R

00477

120

2

30

Minimum Thermal Average Phase C Power Factor Quadrant 3

2.999

/ 2.000

0.001 PF

F8

R

00478

121

0

30

Minimum Thermal Average Power Factor Quadrant 3

2.999

/ 2.000

0.001 PF

F8

R

00479

122

0

30

Minimum Thermal Average Phase A Power Factor Quadrant 4

3.999

/ 3.000

0.001 PF

F8

R

00480

122

1

30

Minimum Thermal Average Phase B Power Factor Quadrant 4

3.999

/ 3.000

0.001 PF

F8

R

00481

122

2

30

Minimum Thermal Average Phase C Power Factor Quadrant 4

3.999

/ 3.000

0.001 PF

F8

R

00482

123

0

30

Minimum Thermal Average Power Factor Quadrant 4

3.999

/ 3.000

0.001 PF

F8

R

00483

124

0

30

Minimum Thermal Average Voltage Imbalance

+327.67% / -327.68%

0.01%

F10

R

00484

124

1

30

Minimum Thermal Average Current Imbalance

+327.67% / -327.68%

0.01%

F10

R

00485

125

0

30

Minimum THD Phase A-N Voltage / Phase A-B Voltage

+327.67% / -327.68%

0.01%

F10

R

00486

125

1

30

Minimum THD Phase B-N Voltage / Phase B-C Voltage

+327.67% / -327.68%

0.01%

F10

R

00487

125

2

30

Minimum THD Phase C-N Voltage / Phase C-A Voltage

+327.67% / -327.68%

0.01%

F10

R

00488

126

0

30

Minimum THD Phase A Current

+327.67% / -327.68%

0.01%

F10

R

00489

126

1

30

Minimum THD Phase B Current

+327.67% / -327.68%

0.01%

F10

R

00490

126

2

30

Minimum THD Phase C Current

+327.67% / -327.68%

0.01%

F10

R

00491

127

0

30

Minimum K-Factor Phase A Current

+327.67% / -327.68%

0.01%

F10

R

00492

127

1

30

Minimum K-Factor Phase B Current

+327.67% / -327.68%

0.01%

F10

R

00493

127

2

30

Minimum K-Factor Phase C Current

+327.67% / -327.68%

0.01%

F10

R

00494-00495

128

0

30

Coincident Thermal Average VAR for Minimum Positive Watt

+32767 VAR / -32768 VAR

1/ 65536 W sec

F7

R

00496-00497

128

1

30

Coincident Thermal Average VAR for Minimum Negative Watt

+32767 VAR / -32768 VAR

1/ 65536 W sec

F7

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum Time Stamp Block

 

 

 

 

 

00498-00501

129

0

50

Maximum Thermal Average Phase A-N Voltage Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

00502-00505

129

1

50

Maximum Thermal Average Phase B-N Voltage Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

00506-00509

129

2

50

Maximum Thermal Average Phase C-N Voltage Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

00510-00513

129

3

50

Maximum Thermal Average Auxiliary Voltage Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

00514-00517

129

4

50

Maximum Thermal Average Phase A Current Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

2- 8

Page 38
Image 38