8.93: Auto Increment Window Block (39423-39488)

„Auto Increment Configuration - 1 Register, 2 bytes.

When read, this register returns the configuration in use by the Auto Increment Log Window, below, to access logs on this port. When written, this register sets the configuration used by the Auto Increment Log Window, below, to access logs on this port. Each port accesses a separate, independent configuration through this register allowing all four ports to access logs with different configurations.

The least significant byte indicates which log is being accessed. The appropriate values are:

0x000

Historical Log 1

0x001

Historical Log 2

0x002

Sequence of Events State Log

0x003

Sequence of Events Snapshot Log

0x004

Digital Input State Log

0x005

Digital Input Snapshot Log

0x006

Digital Output State Log

0x007

Digital Output Snapshot Log

0x008

Flicker Log

0x009

Waveform Trigger Log

0x00A

System Event Log

0x00B

Waveform Sample Log

0x00C

PQ Log

0x00D

Reset Log

0x00E-0x0FF

Undefined

The most significant byte defines the following modes: Paused Download Mode (0x000) and Running Download Modde (0x001).

In Paused Download mode (0x000), the log being accessed is paused - new records are not added to the log while it is paused.

In Running Download mode (0x001), the log being accessed is not paused - new records may be added to the log. When downloading in this mode, it is possible that records may be overwritten before, or even during, access to that record.

„Auto Increment Window Index - 1 register, 2 bytes.

When read, this register returns the index used by the Auto Increment Log Window, below, to access logs on this port. When written, this register sets the index used by the Auto Increment Log Window, below, to access logs on this port. Each port accesses a separate, independent index through this register, allowing all four ports to access different areas of logs at the same time.

When read, the index is incremented before being returned in the Modbus response. If the Auto Increment Mode is Paused Download mode (0x001xx in register 39423, 0x099FE), the appropriate log is paused, preventing the addition of new records while the log is being accessed. A 30-second

8-23

Page 377
Image 377
GE EPM 9650/9800 manual Auto Increment Window Block, „ Auto Increment Configuration 1 Register, 2 bytes