Firmware Variation Strings (65089-65280)

Eight Registers each and Null Terminated ASCII Strings (Terminating Null (ASCII 00H) at the end of the string). (See 3.1.)

8.105: DSP Diagnostic Block (65281-65312)

Description: DSP Diagnostic Registers are for internal use only. These Registers are not for customer use. These Registers are READ ONLY and cannot be written.

8.106: Password Block (65316-65344)

Description: Password Registers included in this block:

User Password (65316-65320):When Passwords are Enabled, a user must write the appropriate Password to these Registers. After the Password is written, the Password State is updated to reflect whether the entered Password matches either of the programmed Passwords. Correct entry of a Password is valid for 2 minutes. Correct entry of a Password is valid only for the port that received the Password.

Password State (65321): This Register contains an enumeration that reports the state of Password Protection on the device. The enumeration is as follows:

0x000

Internal Error

0x001

Obsolete Designation, should not occur

0x002

Password Protection Enabled (None/Wrong Password)

0x003

Level 1 Password

0x004

Level 2 Password

0x005

Password Protection Disabled

0x006

Hardware Defeat

Password State must be combined with Sealing Switch State to determine if a feature is available or not.

Sealing Switch State (65322)

This Register contains an enumeration that reports the State of Sealing Switch Protection on the device. The enumeration is as follows:

0x000

Internal Error

0x001

Sealing Switch Enabled - Not Pressed

0x002

Sealing Switch Enabled - Pressed

0x003

Sealing Switch Disabled

0x004

Sealing Switch Not Installed

0x005

Hardware Defeat

Sealing Switch State must be combined with Password State to determine if a feature is available or not.