8-34
Firmware Variation Strings (65089-65280)
Eight Registers each and Null Terminated ASCII Strings (Terminating Null (ASCII 00H) at the end
of the string). (See 3.1.)
8.105: DSP Diagnostic Block (65281-65312)
QDescription: DSP Diagnostic Registers are for internal use only. These Registers are not for
customer use. These Registers are READ ONLYand cannot be written.
8.106: Password Block (65316-65344)
QDescription: Password Registers included in this block:
User Password (65316-65320): When Passwords are Enabled, a user must write the appropriate
Password to these Registers. After the Password is written, the Password State is updated to reflect
whether the entered Password matches either of the programmed Passwords. Correct entry of a
Password is valid for 2 minutes. Correct entry of a Password is valid only for the port that received
the Password.
Password State (65321): This Register contains an enumeration that reports the state of Password
Protection on the device. The enumeration is as follows:
0x000 Internal Error
0x001 Obsolete Designation, should not occur
0x002 Password Protection Enabled (None/Wrong Password)
0x003 Level 1 Password
0x004 Level 2 Password
0x005 Password Protection Disabled
0x006 Hardware Defeat
Password State must be combined with Sealing Switch State to determine if a feature is available or
not.
Sealing Switch State (65322)
This Register contains an enumeration that reports the State of Sealing Switch Protection on the
device. The enumeration is as follows:
0x000 Internal Error
0x001 Sealing Switch Enabled - Not Pressed
0x002 Sealing Switch Enabled - Pressed
0x003 Sealing Switch Disabled
0x004 Sealing Switch Not Installed
0x005 Hardware Defeat
Sealing Switch State must be combined with Password State to determine if a feature is available or
not.