3.65: Type F65 Scaled Energy Setting

Length: 1/2 a Register (1 byte)

Each register contains 2 bytes. Each byte contains settings for a base quantity. The format of a byte is as follows:

Bit

7

6

5

4

3

2

1

0

Meaning

 

Digits

 

 

Unit

 

Decimal Places

 

Digits is a 3-bit field, which is offset by 2 to represent from 2 to 9 displayable digits.

Unit is a 2-bit field, where the values from 0 to 2 represent units of Wh (100), k (103) and M (106). The value 3 is undefined and is treated the same as 2, signifying M (106).

Decimal Places is a 3-bit field, where the bits represent from 0 to 7 decimal places.

Examples:

For the following, the Q1234 VAh has a current value internally of 123,456,789.0123 VAh.

Register CA00H

 

 

 

 

Reading in Register

 

Digits

Unit

D.P.

Pattern

1AFFH-1B00H

Display

 

 

 

 

 

 

Hex

Binary

 

 

 

 

Hex

Decimal

 

20xxH

001 00 000 3 digits

VAh, 100

0

xxx VAh

00000315H

789

789 VAh

8BxxH

100 01 011

6 digits

kVAh, 103

3

xxx.xxx kVAh 0006F855H

456789

456.789 kvAh

88xxH

100 01 000

6 digits

kVAh, 103

0

xxxxxx kVAh 0001E240H

123456

123,456 kVAh

93xxH

100 10 011

6 digits

MVAh, 106

3

xxx.xxx MVAh 0001E240H

123456

123.456 MVAh

72xxH

011 10 010

5 digits

MVAh, 106

2

xxx.xx MVAh 00003039H

12345

123.45 MVAh

C2xxH

110 00 010

8 digits

VAh, 100

2

xxxxxx.xx VAh 02B90135H

45678901

456,789.01 VAh

The Scaled Energy Programmable Setting can be accessed by clicking:

Device Profile > Revenue & Energy Settings > Energy Scaling.

3-42

Page 260
Image 260
GE EPM 9650/9800 manual Type F65 Scaled Energy Setting, Bit Meaning